Inspections for the day of: Monday, July 11, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00647 FIR-Aging Inspection7/11/20057/11/20057/12/2005 9:59:33 AM CANC
FIR03-00624 FIR-Aging Inspection7/11/20057/11/20057/12/2005 9:45:26 AM NR
Inspection to be called in next wednesday or thursday.
FIR05-00156 INSP-Final Inspection7/11/20057/11/20057/12/2005 8:19:53 AMPFAIL
Provide filter in the duct detector located at hvac unit #34, provide signage on riser room door, provide knox key box, test elevator recall, provide delay for shunt trip, resubmit plans showing the new devices, provide print out of alarm signals, the alarm bell turns on and off when water is flowing, provide map at facp, monitoring company has wrong site address.
FIR04-00684 INSP-Sprinkler Rough-in/Hydro7/11/20057/11/20057/11/2005 3:41:19 PMPFAIL
Inspection was for the drive through canopy. Need eq bracing for the sprig ups and one additional upright at the east overbuild. Also the third and second floor corridors are ok to cover.
BLD05-00086 FIRE-Final Inspection7/11/20057/11/20057/11/2005 3:38:58 PMPPASS
Permit finaled. Per IFC chapter 23 flue spaces not required.
FIR05-00274 INSP-Final Inspection7/8/20057/11/20057/11/2005 12:02:59 PMAPASS
fire sprinkler finaled
FIR02-00051 INSP-Final Inspection7/7/20057/11/20057/11/2005 9:23:31 AMAPASS
Fire alarm permit finaled