Inspections for the day of: Tuesday, July 11, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00338 INSP-Sprinkler Rough-in7/10/20067/11/20067/11/2006 3:52:01 PMPPASS
Sprinkler piping is ok to cover but there are corrections that need to be done. See approved plans for locations. This will be verified at final.
FIR06-00318 INSP-Sprinkler Rough-in7/10/20067/11/20067/11/2006 3:50:40 PMPPASS
Sprinkler piping is ok to cover.
FIR02-00113 INSP-Final Inspection7/11/20067/11/20067/11/2006 3:49:59 PMPPASS
Upon visual inspection I found that the work had either been installed and later removed or never installed at all. The doors as shown on the plans do not exist.
BLD05-02671 FIRE-Final Inspection7/10/20067/11/20067/11/2006 2:21:08 PMPFAIL
Provide signage at the property entrance as discussed and provide the indicator at the lock on the main entrance/exit door.
FIR05-00536 INSP-Sprinkler Rough-in7/11/20067/11/20067/11/2006 1:47:06 PMPPASS
The 8" city supply underground for the project is ok to cover. The two 8" elbows did not need to be installed.
BLD04-00917 FIRE-Final Inspection7/10/20067/11/20067/11/2006 1:20:56 PMAPASS
life safety finaled
BLD06-00756 FIRE-Final Inspection7/10/20067/11/20067/11/2006 8:52:02 AMAPASS
Life safety finaled