BLD11-02834
| FIRE-Final Inspection | 7/11/2012 | 7/11/2012 | 7/11/2012 3:59:39 PM | P | PEND |
|
|
|
FIR12-00102
| INSP-Sprinkler Rough-in | 7/10/2012 | 7/11/2012 | 7/11/2012 3:57:34 PM | P | PART |
|
|
Completed remainder of overhead rough-in at system #5. Heads at the upper level of the return plenum are not installed as indicated on approved plans. Seismic bracing and retainers are complete. Pendent head spacing at the north corridor adjusted to meet ft2 designed.
|
FIR12-00192
| INSP-Final Inspection | 7/11/2012 | 7/11/2012 | 7/11/2012 3:51:15 PM | P | PASS |
|
|
Scope of permit work passed final walkthrough. Fire sprinkler permit finaled.
|
BLD12-01401
| FIRE-Final Inspection | 7/10/2012 | 7/11/2012 | 7/11/2012 2:56:56 PM | P | PASS |
|
|
Correction items completed. Life safety passed.
|
BLD12-01261
| FIRE-Final Inspection | 7/11/2012 | 7/11/2012 | 7/11/2012 2:44:14 PM | P | PASS |
|
|
|
BLD12-01261
| FIRE-Conference | 7/11/2012 | 7/11/2012 | 7/11/2012 2:38:27 PM | P | DONE |
|
|
please call before going donna ###-####
|
BLD12-01662
| FIRE-Final Inspection | 7/11/2012 | 7/11/2012 | 7/11/2012 12:10:54 PM | P | PASS |
|
|
Noted correction items verified for completion. Life safety passed.
|
BLD11-03041
| FIRE-Final Inspection | 7/10/2012 | 7/11/2012 | 7/11/2012 11:19:52 AM | A | PASS |
|
|
Fire life safety finaled.
|
FIR12-00352
| INSP-Sprinkler Rough-in | 7/10/2012 | 7/11/2012 | 7/11/2012 11:12:41 AM | A | PART |
|
|
Overhead fire sprinkler work is approved for ceiling cover.
|
BLD11-01486
| FIRE-Final Inspection | 7/10/2012 | 7/11/2012 | 7/11/2012 11:10:41 AM | A | FAIL |
|
|
Noted correction items include; post three 2A10BC fire extinguishers with current certification tags at locations indicated on plan sheet A1.2 keynote #29, repair exit discharge light at the main entry landing, one light bulb at the EM light SE second exit is not functional, posted building address does not match permit documents. Need to verify existing duct detectors are operational.
|
FIR12-00332
| INSP-Sprinkler Rough-in | 7/10/2012 | 7/11/2012 | 7/10/2012 4:50:59 PM | A | CANC |
|
|
This is an ug to cover. Richard is the contact. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|