ELE12-00443
| ELE-Aging Inspection | 7/11/2013 | 7/11/2013 | 7/11/2013 2:36:45 PM | | DONE |
|
|
still under construction
|
GCE13-00112
| GCE-Rough-In | 7/11/2013 | 7/11/2013 | 7/11/2013 1:58:27 PM | P | PASS |
|
|
###-#### Pool pump rough-in ok cover pool underground and bonding
|
ELE13-01803
| Final | 7/11/2013 | 7/11/2013 | 7/11/2013 1:38:44 PM | P | PASS |
|
|
job complete, final ok
|
ELE13-01803
| Electrical Rough-In | 7/11/2013 | 7/11/2013 | 7/11/2013 1:37:23 PM | P | PASS |
|
|
Any questions, please call Clay. Thanks! Phone #: ###-#### >> Inspection requested via web by Clay Morgan rough-in ok power for gas furnace, A/C unit
|
ELE13-00580
| Final | 7/11/2013 | 7/11/2013 | 7/11/2013 1:28:24 PM | P | FAIL |
|
|
Enrique Phone #: ###-#### NEC 210.52(B)(2) Shall have a minimum of two applance circuits serving kitchen counter tops.NEC 406.11 All 15 and 20 ampere receptacles shall be listed tamper resistance in dwelling units. NEC 210.8 Receptacles within 6 ft. of an sink or basin require GFCI protection
|
ELE13-01573
| Permanent Service | 7/11/2013 | 7/11/2013 | 7/11/2013 12:41:54 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Nick Larson p/s o/h rec ok relocate grounds min.6 ft apart for final,label panel directory
|
ELE13-01271
| Electrical Rough-In | 7/11/2013 | 7/11/2013 | 7/11/2013 12:02:02 PM | P | PASS |
|
|
underground - dirk Phone #: ###-#### rough-in ok cover underground conduits from building to dispenser pumps to product tanks.
|
ELE13-01506
| Electrical Rough-In | 7/10/2013 | 7/11/2013 | 7/11/2013 10:17:35 AM | A | PASS |
|
|
Wall inspection. PET/CT Scanner 1st floor. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover
|
ELE13-01605
| Electrical Rough-In | 7/10/2013 | 7/11/2013 | 7/11/2013 9:39:08 AM | A | PASS |
|
|
Javier Phone #: ###-#### rough-in ok cover trench to water feature
|
ELE13-01792
| Final | 7/10/2013 | 7/11/2013 | 7/11/2013 9:27:24 AM | A | NR |
|
|
Please call Ron Vreeland if any questions Phone #: ###-#### >> Inspection requested via web by brad williams not ready at this time
|
ELE13-01792
| Permanent Service | 7/11/2013 | 7/11/2013 | 7/11/2013 9:25:39 AM | A | PASS |
|
|
p/s o/h rec ok
|
ELE13-01797
| Electrical Rough-In | 7/10/2013 | 7/11/2013 | 7/11/2013 8:57:32 AM | A | PASS |
|
|
Geoff Hannaford is contact ###-####, grounding inspection.. Phone #: ###-#### >> Inspection requested via web by Debby Ellis rough-in ok cover # 2 cu concrete encased electrode
|
ELE13-01009
| Final | 7/10/2013 | 7/11/2013 | 7/11/2013 8:36:22 AM | A | PASS |
|
|
garage code 0243 Phone #: ###-#### >> Inspection requested via web by Heath Thomas final ok
|
ELE13-00628
| Final | 7/10/2013 | 7/11/2013 | 7/11/2013 8:35:45 AM | A | PASS |
|
|
garage code 0243 Phone #: ###-#### >> Inspection requested via web by Heath Thomas final ok
|
ELE13-01271
| Electrical Rough-In | 7/8/2013 | 7/11/2013 | 7/11/2013 8:24:06 AM | A | FAIL |
|
|
underground - Dirk Phone #: ###-#### Trench covered before inspection, uncover trench in two locations
|
ELE11-01094
| Conference | 7/10/2013 | 7/11/2013 | 7/10/2013 3:52:46 PM | A | DONE |
|
|
kevin rough-in completed at time of conference, Discussed requirements for service upgrade.
|