Inspections for the day of: Thursday, July 11, 2013.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00443 ELE-Aging Inspection7/11/20137/11/20137/11/2013 2:36:45 PM DONE
still under construction
GCE13-00112 GCE-Rough-In7/11/20137/11/20137/11/2013 1:58:27 PMPPASS
###-#### Pool pump rough-in ok cover pool underground and bonding
ELE13-01803 Final7/11/20137/11/20137/11/2013 1:38:44 PMPPASS
job complete, final ok
ELE13-01803 Electrical Rough-In7/11/20137/11/20137/11/2013 1:37:23 PMPPASS
Any questions, please call Clay. Thanks! Phone #: ###-#### >> Inspection requested via web by Clay Morgan rough-in ok power for gas furnace, A/C unit
ELE13-00580 Final7/11/20137/11/20137/11/2013 1:28:24 PMPFAIL
Enrique Phone #: ###-#### NEC 210.52(B)(2) Shall have a minimum of two applance circuits serving kitchen counter tops.NEC 406.11 All 15 and 20 ampere receptacles shall be listed tamper resistance in dwelling units. NEC 210.8 Receptacles within 6 ft. of an sink or basin require GFCI protection
ELE13-01573 Permanent Service7/11/20137/11/20137/11/2013 12:41:54 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Nick Larson p/s o/h rec ok relocate grounds min.6 ft apart for final,label panel directory
ELE13-01271 Electrical Rough-In7/11/20137/11/20137/11/2013 12:02:02 PMPPASS
underground - dirk Phone #: ###-#### rough-in ok cover underground conduits from building to dispenser pumps to product tanks.
ELE13-01506 Electrical Rough-In7/10/20137/11/20137/11/2013 10:17:35 AMAPASS
Wall inspection. PET/CT Scanner 1st floor. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover
ELE13-01605 Electrical Rough-In7/10/20137/11/20137/11/2013 9:39:08 AMAPASS
Javier Phone #: ###-#### rough-in ok cover trench to water feature
ELE13-01792 Final7/10/20137/11/20137/11/2013 9:27:24 AMANR
Please call Ron Vreeland if any questions Phone #: ###-#### >> Inspection requested via web by brad williams not ready at this time
ELE13-01792 Permanent Service7/11/20137/11/20137/11/2013 9:25:39 AMAPASS
p/s o/h rec ok
ELE13-01797 Electrical Rough-In7/10/20137/11/20137/11/2013 8:57:32 AMAPASS
Geoff Hannaford is contact ###-####, grounding inspection.. Phone #: ###-#### >> Inspection requested via web by Debby Ellis rough-in ok cover # 2 cu concrete encased electrode
ELE13-01009 Final7/10/20137/11/20137/11/2013 8:36:22 AMAPASS
garage code 0243 Phone #: ###-#### >> Inspection requested via web by Heath Thomas final ok
ELE13-00628 Final7/10/20137/11/20137/11/2013 8:35:45 AMAPASS
garage code 0243 Phone #: ###-#### >> Inspection requested via web by Heath Thomas final ok
ELE13-01271 Electrical Rough-In7/8/20137/11/20137/11/2013 8:24:06 AMAFAIL
underground - Dirk Phone #: ###-#### Trench covered before inspection, uncover trench in two locations
ELE11-01094 Conference7/10/20137/11/20137/10/2013 3:52:46 PMADONE
kevin rough-in completed at time of conference, Discussed requirements for service upgrade.