Inspections for the day of: Friday, July 11, 2014.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01198 ELE-Aging Inspection7/11/20147/11/20147/14/2014 1:37:32 PM DONE
left message
ELE14-01742 Electrical Rough-In7/11/20147/11/20147/11/2014 3:40:13 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Dan Surerus 300.4(A) 11/4" to nearest edge of NM cable . need nailplates throughout remodel area
ELE14-00776 Final7/11/20147/11/20147/11/2014 3:00:06 PMPFAIL
John Harvey is out of town. Contact Tim Beaudoin (general contractor) I''d any problems. House is open and there are people working in the house


Phone #: ###-#### >> Inspection requested via web by John Harvey reverse polarity in garage outlets and some without GFCI protection. GFCI protection required in upst. bathroom near toilet. Finish trim in upst. bbrm., Open boxes in bsmt.
ELE14-00793 Electrical Rough-In7/11/20147/11/20147/11/2014 1:46:46 PMPPASS
floor heat / Mike Phone #: ###-#### r/i floor heat ok
ELE14-00629 Permanent Service7/10/20147/11/20147/11/2014 1:16:17 PMPPASS
Larry Phone #: ###-#### p/s o/h n ok
ELE14-00982 Final7/10/20147/11/20147/11/2014 12:34:05 PMAFAIL
Garage code 6675 Phone #: ###-#### >> Inspection requested via web by Dan Rohl Kitchen counter outlets need 314.20- kitchen and entertainment center. Reverse polarity in bathroom outlets. Upst. shower recessed have shower trim?? Circuit 14 AFCI not working, 50% energy efficient lamps required.
ELE14-01064 Final7/11/20147/11/20147/11/2014 11:33:54 AMPPASS
Kevin Phone #: ###-#### final ok
ELE14-01601 Electrical Rough-In7/10/20147/11/20147/11/2014 11:32:38 AMPPASS
Jerad-floor heat Phone #: ###-#### r/i ok upst. floor heat
ELE14-01628 Electrical Rough-In7/11/20147/11/20147/11/2014 10:55:14 AMPPASS
Floor heat insp. It will be ready late morning and can be inspected any time. Phone #: ###-#### >> Inspection requested via web by Eric Brown r/i ok floor heat
ELE14-01805 Electrical Rough-In7/11/20147/11/20147/11/2014 10:38:26 AMAPASS
this inspection is for the detached garage---for cover only Phone #: ###-#### >> Inspection requested via web by ron spen cer r/i shop ok
ELE14-01183 Electrical Rough-In7/11/20147/11/20147/11/2014 10:17:53 AMAPASS
Call mike 30 min. Prior to inspection ###-#### Phone #: ###-#### >> Inspection requested via web by Mike Basye r/i ceilings ok 2nd floor area B and C and 3rd floor n.west FBI area
ELE14-01208 Final7/10/20147/11/20147/11/2014 9:38:02 AMAPASS
Boise City has finaled this out and it has been energized. I am unsure if it is necessary to have a final inspection, but it shows on my list as not finaled. Phone #: ###-#### >> Inspection requested via web by Bryan Atkins final ok
ELE14-01887 Final7/11/20147/11/20147/11/2014 9:15:10 AMACANC
>> Inspection requested via web by Charles Davis needed r/i
ELE14-01887 Electrical Rough-In7/11/20147/11/20147/11/2014 9:14:41 AMPPASS
>> Inspection requested via web by Charles Davis r/i ok kitchen ,bath and old closet
ELE14-01884 Final7/10/20147/11/20147/10/2014 3:54:29 PMPCANC
New A/C is on right hand side of garage and gate will open with a screw driver to reach through and flip latch. Phone #: ###-#### >> Inspection requested via web by Mike Cole Inspection cancelled from web by: Mike Cole
ELE14-01682 Electrical Rough-In7/10/20147/11/20147/10/2014 2:36:18 PMAPASS
Please inspect underground for cover Phone #: ###-#### >> Inspection requested via web by Spencer McLean slab conduit ok to cover