Inspections for the day of: Friday, July 11, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00222 INSP-Supply line flush7/11/20147/11/20147/11/2014 3:28:47 PMPCANC
Cancel per Anthony Minichiello
BLD13-02436 FIRE-Final Inspection7/11/20147/11/20147/11/2014 3:27:37 PMPPASS
life safety passed
BLD13-02437 FIRE-Final Inspection7/11/20147/11/20147/11/2014 3:27:15 PMPPASS
life safety passed
BLD14-01867 FIRE-Final Inspection7/11/20147/11/20147/11/2014 1:16:54 PMPPASS
Life safety passed. Deadbolt to be removed from the rear exit door and single action hardware to be provided on doors "D1"
FIR13-00494 INSP-Final Inspection7/10/20147/11/20147/11/2014 1:12:27 PMAPASS
Permit finaled
BLD14-01908 FIRE-Final Inspection7/10/20147/11/20147/11/2014 10:43:59 AMAFAIL
Provide sticker at the main exit and a tagged fire extinguisher for the office area mezzanine.
BLD14-01722 FIRE-Final Inspection7/9/20147/11/20147/11/2014 10:43:15 AMAPASS
life safety passed
BLD13-02436 FIRE-Final Inspection7/10/20147/11/20147/11/2014 8:34:19 AMAFAIL
Provide city approved plans and small documents
BLD13-02437 FIRE-Final Inspection7/10/20147/11/20147/11/2014 8:33:52 AMAPASS
Provide city approved plans and small documents.
BLD13-02416 FIRE-Final Inspection7/10/20147/11/20147/11/2014 8:33:18 AMAFAIL
Strobe coverage has been blocked by the new door. Provide additional coverage with-in 15'-0" of the end of the corridor including coverage in the pocket. See NFPA 72 18.5.5.5.5.

Smoke detector coveage has been blocked by the new door. Provide additional smoke detector coverage as per NFPA 72 17.5.3.1 and 17.6.3.1.1.

Provide city approved plans and small documents.