FIR14-00222
| INSP-Supply line flush | 7/11/2014 | 7/11/2014 | 7/11/2014 3:28:47 PM | P | CANC |
|
|
Cancel per Anthony Minichiello
|
BLD13-02436
| FIRE-Final Inspection | 7/11/2014 | 7/11/2014 | 7/11/2014 3:27:37 PM | P | PASS |
|
|
life safety passed
|
BLD13-02437
| FIRE-Final Inspection | 7/11/2014 | 7/11/2014 | 7/11/2014 3:27:15 PM | P | PASS |
|
|
life safety passed
|
BLD14-01867
| FIRE-Final Inspection | 7/11/2014 | 7/11/2014 | 7/11/2014 1:16:54 PM | P | PASS |
|
|
Life safety passed. Deadbolt to be removed from the rear exit door and single action hardware to be provided on doors "D1"
|
FIR13-00494
| INSP-Final Inspection | 7/10/2014 | 7/11/2014 | 7/11/2014 1:12:27 PM | A | PASS |
|
|
Permit finaled
|
BLD14-01908
| FIRE-Final Inspection | 7/10/2014 | 7/11/2014 | 7/11/2014 10:43:59 AM | A | FAIL |
|
|
Provide sticker at the main exit and a tagged fire extinguisher for the office area mezzanine.
|
BLD14-01722
| FIRE-Final Inspection | 7/9/2014 | 7/11/2014 | 7/11/2014 10:43:15 AM | A | PASS |
|
|
life safety passed
|
BLD13-02436
| FIRE-Final Inspection | 7/10/2014 | 7/11/2014 | 7/11/2014 8:34:19 AM | A | FAIL |
|
|
Provide city approved plans and small documents
|
BLD13-02437
| FIRE-Final Inspection | 7/10/2014 | 7/11/2014 | 7/11/2014 8:33:52 AM | A | PASS |
|
|
Provide city approved plans and small documents.
|
BLD13-02416
| FIRE-Final Inspection | 7/10/2014 | 7/11/2014 | 7/11/2014 8:33:18 AM | A | FAIL |
|
|
Strobe coverage has been blocked by the new door. Provide additional coverage with-in 15'-0" of the end of the corridor including coverage in the pocket. See NFPA 72 18.5.5.5.5.
Smoke detector coveage has been blocked by the new door. Provide additional smoke detector coverage as per NFPA 72 17.5.3.1 and 17.6.3.1.1.
Provide city approved plans and small documents.
|