ELE13-03227
| ELE-Aging Inspection | 7/11/2018 | 7/11/2018 | 7/13/2018 3:49:44 PM | | CANC |
|
|
too busy
|
ELE13-03214
| ELE-Aging Inspection | 7/11/2018 | 7/11/2018 | 7/13/2018 10:10:33 AM | | PASS |
|
|
permit expired
|
ELE17-02649
| Electrical Rough-In | 7/10/2018 | 7/11/2018 | 7/12/2018 7:29:45 AM | P | PASS |
|
|
Ceiling inspection - contact is Andy Chambers Phone #: ###-#### Inspection requested via web by Scott Campbell...rms marked on plans
|
ELE18-01021
| Final | 7/11/2018 | 7/11/2018 | 7/11/2018 2:29:56 PM | P | PASS |
|
|
access 2569 Phone #: ###-#### Inspection requested via web by David Nelson...ok to final
|
ELE18-02606
| Electrical Rough-In | 7/11/2018 | 7/11/2018 | 7/11/2018 1:54:10 PM | P | PASS |
|
|
wall rough in. Chad VanOrden is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce...1 new wall switch and outlet...ok to cover
|
ELE18-02445
| Electrical Rough-In | 7/11/2018 | 7/11/2018 | 7/11/2018 12:37:46 PM | P | PASS |
|
|
Tom-underground conduit Phone #: ###-####...ok to cover
|
ELE18-01167
| Final | 7/11/2018 | 7/11/2018 | 7/11/2018 12:16:46 PM | P | FAIL |
|
|
access 6935 Phone #: ###-#### Inspection requested via web by David Nelson... unit 1..abrasion protection needs added for romex at bedroom heaters unit 2..romex protection-heaters outlets shall not be installed above heater unit 3..romex protection-heaters outlets shall not be installed above heater unit 4 romex protection-heaters outlets shall not be installed above heater unit 5..abrasion protection for romex living heater unit 6..patio light not working romex protection-heaters unit 7..living rm heater-junction cover kitchen outlets need to be completed panel needs labelled completely unit 8..panel needs labelled completely
|
ELE14-00678
| ELE-Aging Inspection | 7/11/2018 | 7/11/2018 | 7/11/2018 11:17:57 AM | | PASS |
|
|
final scheduled and resulted
|
ELE14-00678
| Final | 7/11/2018 | 7/11/2018 | 7/11/2018 11:17:35 AM | P | PASS |
|
|
UL listing verified and disconnect ok
|
ELE17-02445
| Final | 7/10/2018 | 7/11/2018 | 7/11/2018 11:00:18 AM | A | PART |
|
|
Please call Mike. Phone #: ###-#### Inspection requested via web by Kevin Perez..marked areas ceiling grids and classrooms...rm 116 1 GFCI needed, exterior outlets WR GFCI, hall 119 GFCI protection for vending machines, HVAC disconnects circuit labelling and service outlet needed
|
ELE18-02545
| Conference | 7/9/2018 | 7/11/2018 | 7/11/2018 9:45:48 AM | A | PASS |
|
|
If you can give me 30 minutes notice the homeowner will let us in. Thank You. Phone #: ###-#### Inspection requested via web by Craig Korell...discussed service change, existing panel changed to junction box-access oked, service lateral over shed-raise riser to get clearance as much as possible-shed not a permanent structure
|
ELE18-02048
| Electrical Rough-In | 7/10/2018 | 7/11/2018 | 7/11/2018 9:22:51 AM | A | PASS |
|
|
Austin Jensen, crew lead: ###-#### The install is taking place on 7/11. Phone #: ###-#### Inspection requested via web by BRS Permitting...UL listed equipment verified...30A breaker will be installed in panel
|
ELE18-02484
| Electrical Rough-In | 7/10/2018 | 7/11/2018 | 7/11/2018 8:50:50 AM | A | PASS |
|
|
rough-in of 2 offices and some wiring on west wall of deck plus north and west wall in warehouse, Thanks Phone #: ###-#### Inspection requested via web by Rick Beckman...rough ok to cover...verify breaker l/o or disconnect on water heater at final
|
ELE18-01912
| Permanent Service | 7/10/2018 | 7/11/2018 | 7/11/2018 8:19:33 AM | A | PASS |
|
|
Service inspection pedestal for parking lot lighting. Please contact Cory Sells if needed - ###-#### (I hope I chose the correct insp type) thanks, cyndi Phone #: ###-#### Inspection requested via web by Cyndi Dale...p/s u/g new ok
|