Inspections for the day of: Friday, July 12, 2002.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01541 Final7/11/20027/12/20027/12/2002 12:00:00 AMAPASS
final for x ray machine ###-#### final ok x-ray unit field evaluated by U L 7/12/2002 11:28:30 AM
ELE01-03021 Electrical Rough-In7/11/20027/12/20027/12/2002 12:00:00 AMAPART
russel ###-#### part for u/g conduit ok 7/12/2002 12:17:27 PM
ELE02-02127 Rough-In Permanent Service7/11/20027/12/20027/12/2002 12:00:00 AMAFAIL
###-#### correction posted called 300.4(A)(1)&(D), 314.20, 210.52(F)&210.11(C)(2), 250.52(A)(1), 110.3(A)(4) replace damaged romex wall between laundryand dinning by outside wall 14/2410.15 secure reccess lights stairwell, 314.16 box fill 2 gang top of stairs C O W 7/12/2002 11:01:01 AM
ELE02-01889 Electrical Rough-In7/11/20027/12/20027/12/2002 12:00:00 AMAPASS
meeting 8:00 too 8:30 r/i ok 7/12/2002 10:28:19 AM
ELE02-02110 Electrical Rough-In7/11/20027/12/20027/12/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 07/11/2002 at 21:21:00. Contact: ###-####. corrections made r/i ok see added p/s 7/12/2002 12:58:33 PM
ELE02-00484 Final7/12/20027/12/20027/12/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 07/12/2002 at 07:46:33. Contact: ###-####. ok 7/12/2002 3:31:26 PM
ELE02-01415 Final7/12/20027/12/20027/12/2002 12:00:00 AMPFAIL
###-#### no access notice posted called , it is the wrong number 7/12/2002 5:51:25 PM
ELE02-02109 Rough-In Permanent Service7/12/20027/12/20027/12/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 07/12/2002 at 08:40:28. Contact: ###-####. corrections not made needs 300.(A)(1)and(D) and 314.20 set boxes flush with finish surface talked with contractor at job site he called electrical contractor 7/12/2002 2:57:16 PM
ELE02-02088 Rough-In Permanent Service7/12/20027/12/20027/12/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 07/12/2002 at 10:51:03. Contact: ###-####. cor. posted called left message 230.24(A) exception #3 needs 18 inches for drip loop from roof, 110.3(B) vacuum outlets state non metallic raceways only, 312.2 needs hub for PVC exiting top of service panel, strap rigid and pvc 7/12/2002 5:18:24 PM
ELE02-02110 Permanent Service7/12/20027/12/20027/12/2002 12:00:00 AMPPASS

p/s u/g new ok
ELE02-01973 Final7/12/20027/12/20027/12/2002 12:00:00 AMPPASS
final ok for all 3 spaces #105, #106, #107 7/12/2002 4:12:26 PM