Inspections for the day of: Thursday, July 12, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00022 FIR-Aging Inspection7/12/20077/12/20077/13/2007 5:36:32 PM DONE
Under construction, work in progress.
BLD07-00917 FIRE-Conference7/12/20077/12/20077/13/2007 5:32:58 PMPDONE
On site visit, discussed repair of existing emergency lighting at the stairways, project schedule, related fire sprinkler and alarm permits.
BLD07-00293 FIRE-Final Inspection7/11/20077/12/20077/12/2007 2:54:46 PMAPART
Fire life safety final pending sprinkler permit pump acceptance test, okay for TOC with S. Rogers permission.
BLD06-01663 FIRE-Final Inspection7/11/20077/12/20077/12/2007 2:51:17 PMAPART
Temp occupancy approved with S. Rogers permission pending satisfactory pump acceptance testing for the project related fire sprinkler permit to be completed 7/25, also need to add one exit sign at the NE door as indicated on approved plans.
FIR07-00203 INSP-Final Inspection7/11/20077/12/20077/12/2007 2:47:32 PMAPART
Required corrections verified for completion, trip testing passed, resubmittals approved, final pending pump acceptance testing per NFPA 20.
FIR07-00208 INSP-Final Inspection7/11/20077/12/20077/12/2007 2:45:22 PMAPASS
Final corrections have been made, fire alarm work passed inspection, permit finaled.
FIR07-00514 INSP-Sprinkler Rough-in/Hydro7/12/20077/12/20077/12/2007 2:42:39 PMPPART
OH fire sprinkler install is okay for cover at the drop ceilings except where red lined on approved drawings.
FIR07-00505 INSP-Sprinkler Rough-in7/11/20077/12/20077/12/2007 2:41:22 PMAPART
FDC pit and drain are approved.
FIR07-00571 INSP-Sprinkler Rough-in7/11/20077/12/20077/12/2007 2:40:18 PMAPART
Fire sprinkler modifications per the scope of work are approved for cover at the drop ceilings.
BLD07-00824 FIRE-Final Inspection7/11/20077/12/20077/12/2007 2:38:15 PMAPASS
Fire life safety is satisfactory, noted seals at fire doors to be installed when door frame painting is completed, the temporary max. occ. sign is okay until the permanent one arrives, door hardware is approved as discussed.
FIR07-00457 INSP-Final Inspection7/11/20077/12/20077/12/2007 2:34:46 PMAPASS
Fire sprinkler permit finaled.
FIR07-00557 INSP-Sprinkler Rough-in7/11/20077/12/20077/12/2007 2:33:58 PMAPART
TI fire sprinkler modifications are acceptable, rough-in passed.
BLD07-01628 FIRE-Final Inspection7/11/20077/12/20077/12/2007 2:33:02 PMAPASS
Fire life safety inspection passed.
FIR07-00285 INSP-Sprinkler Rough-in7/11/20077/12/20077/12/2007 2:30:49 PMAPART
Heads and piping at the 2nd floor stairway and restroom hard lid ceilings appears satisfactory, however no approved plans were made available on site for verification.