FIR07-00212
| FIR-Aging Inspection | 7/12/2007 | 7/12/2007 | 7/13/2007 12:57:46 PM | | NR |
|
|
Work has not started on the project yet
|
FIR07-00196
| INSP-Supply line flush | 7/12/2007 | 7/12/2007 | 7/13/2007 12:42:42 PM | P | CANC |
|
|
Duplicate inspection
|
FIR07-00595
| INSP-Sprinkler Rough-in | 7/12/2007 | 7/12/2007 | 7/13/2007 9:34:08 AM | P | PASS |
|
|
The underground supply piping from the building out approximately 20' is ok to cover. See the city approved plans for the piping reroute around the building footing. I asked Stan to have his office show this change on the overhead submittals so that it is included in the hydraulic calculations.
|
FIR07-00533
| INSP-Final Inspection | 7/12/2007 | 7/12/2007 | 7/12/2007 12:12:07 PM | P | PASS |
|
|
Permit finaled. An earthquake brace still needs to be installed on the new sprig up. This will be checked at the building final.
|
FIR07-00196
| INSP-Sprinkler Rough-in/Hydro | 7/12/2007 | 7/12/2007 | 7/12/2007 12:08:57 PM | P | PASS |
|
|
The anti-freeze system and underground supply hydro test passed. I also did a life safety walk through with the general contractor.
|
FIR06-00518
| INSP-Final Inspection | 7/11/2007 | 7/12/2007 | 7/12/2007 11:00:49 AM | A | PASS |
|
|
Permit finaled
|
BLD07-00465
| FIRE-Final Inspection | 7/11/2007 | 7/12/2007 | 7/12/2007 10:44:51 AM | A | FAIL |
|
|
Repair exit sign in the store room, provide earthquake bracing on the new sprig up in the store room and provide approved hardware on the restroom door. The smoke evac system and the duct detector performed as required.
|
BLD07-01139
| FIRE-Final Inspection | 7/12/2007 | 7/12/2007 | 7/12/2007 10:43:05 AM | P | PASS |
|
|
Life safety passed.
|
FIR07-00429
| INSP-Final Inspection | 7/11/2007 | 7/12/2007 | 7/12/2007 10:42:34 AM | A | PASS |
|
|
Permit finaled
|
FIR05-00536
| INSP-Sprinkler Rough-in | 7/11/2007 | 7/12/2007 | 7/12/2007 9:06:09 AM | A | PASS |
|
|
The 2" fill line to the secondary storage tank was flushed. Also see the city approved plans for corridors and rooms on the second floor and first floor where piping is ok to cover. I also looked at the piping that will be above the Rulon ceiling in the first floor elevator lobby but did not give the ok to cover since this area has been resubmitted.
|