FIR11-00442
| INSP-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 5:57:31 PM | P | FAIL |
|
|
Items noted during initial acceptance test include; horn only appliances throughout all units on all floors do not meet mounting heights per NFPA 72, need to relocate SD at the 1st and 2nd floor north elevator lobbies, relocate one SD for door hold release at the 1st floor, provide A/V at the1st floor laundry room per plan, repair one WP A/V at the parking garage, post signage at the doors to the FACP room, cd settings at five locations adjusted while on site. Items tested okay include all five ID detectors for damper shutdown, MP at the panel, and notification testing on all floors. Sprinkler monitoring, elevator recall, NAC's, EOL's and panel items not tested.
|
FIR11-00496
| INSP-Final Inspection | 7/12/2012 | 7/12/2012 | 7/12/2012 5:43:39 PM | P | PEND |
|
|
|
FIR12-00324
| INSP-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 5:42:13 PM | P | PEND |
|
|
|
BLD12-01202
| FIRE-Final Inspection | 7/12/2012 | 7/12/2012 | 7/12/2012 5:39:34 PM | P | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
BLD11-00179
| FIRE-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 5:38:29 PM | P | NR |
|
|
Gary ###-#### >> Inspection requested via web by Gary Simon
|
FIR12-00278
| INSP-Final Inspection | 7/12/2012 | 7/12/2012 | 7/12/2012 5:38:03 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR12-00325
| INSP-Final Inspection | 7/10/2012 | 7/12/2012 | 7/12/2012 5:36:26 PM | P | PASS |
|
|
Fire alarm testing passed after one smoke detector relocated while on site. Permit finaled.
|
FIR12-00246
| INSP-Sprinkler Rough-in | 7/12/2012 | 7/12/2012 | 7/12/2012 5:34:02 PM | P | NH |
|
|
Arrived at the jobsite at 4:30- Gate locked, no access
|
FIR12-00332
| INSP-Sprinkler Rough-in | 7/10/2012 | 7/12/2012 | 7/12/2012 5:32:25 PM | P | NR |
|
|
This is an ug to cover. Richard is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
BLD12-00511
| FIRE-Final Inspection | 7/12/2012 | 7/12/2012 | 7/12/2012 5:31:42 PM | A | PASS |
|
|
Fire life safety finaled.
|
FIR09-00059
| INSP-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 5:30:29 PM | A | PASS |
|
|
Fire alarm testing passed. Permit finaled.
|
FIR12-00284
| INSP-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 5:29:10 PM | A | PASS |
|
|
Completed early morning alarm testing per contractor request. Inspection passed, permit finaled.
|
FIR12-00301
| INSP-Final Inspection | 7/10/2012 | 7/12/2012 | 7/12/2012 5:26:37 PM | A | PASS |
|
|
Fire sprinkler permit finaled. One missing escutcheon installed while on site.
|
FIR12-00039
| INSP-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 5:23:16 PM | A | PART |
|
|
LCM cabinets finished with the exception of #5008 yet to be piped. 5000, 5001, 5003-07 and 5009 are complete.
|
FIR12-00210
| INSP-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 5:20:01 PM | A | PASS |
|
|
Scope of work passed final inspection. Fire sprinkler permit finaled.
|
FIR12-00224
| INSP-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 5:18:43 PM | A | PASS |
|
|
Fire sprinkler permit work passed final inspection.
|
FIR12-00039
| INSP-Sprinkler Rough-in/Hydro | 7/11/2012 | 7/12/2012 | 7/12/2012 8:01:18 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by John Wheeler Inspection cancelled from web by: John Wheeler
|