Inspections for the day of: Thursday, July 12, 2012.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00442 INSP-Final Inspection7/11/20127/12/20127/12/2012 5:57:31 PMPFAIL
Items noted during initial acceptance test include; horn only appliances throughout all units on all floors do not meet mounting heights per NFPA 72, need to relocate SD at the 1st and 2nd floor north elevator lobbies, relocate one SD for door hold release at the 1st floor, provide A/V at the1st floor laundry room per plan, repair one WP A/V at the parking garage, post signage at the doors to the FACP room, cd settings at five locations adjusted while on site. Items tested okay include all five ID detectors for damper shutdown, MP at the panel, and notification testing on all floors. Sprinkler monitoring, elevator recall, NAC's, EOL's and panel items not tested.
FIR11-00496 INSP-Final Inspection7/12/20127/12/20127/12/2012 5:43:39 PMPPEND
FIR12-00324 INSP-Final Inspection7/11/20127/12/20127/12/2012 5:42:13 PMPPEND
BLD12-01202 FIRE-Final Inspection7/12/20127/12/20127/12/2012 5:39:34 PMPPASS
Fire life safety inspection completed satisfactory.
BLD11-00179 FIRE-Final Inspection7/11/20127/12/20127/12/2012 5:38:29 PMPNR
Gary ###-#### >> Inspection requested via web by Gary Simon
FIR12-00278 INSP-Final Inspection7/12/20127/12/20127/12/2012 5:38:03 PMPPASS
Fire sprinkler permit finaled.
FIR12-00325 INSP-Final Inspection7/10/20127/12/20127/12/2012 5:36:26 PMPPASS
Fire alarm testing passed after one smoke detector relocated while on site. Permit finaled.
FIR12-00246 INSP-Sprinkler Rough-in7/12/20127/12/20127/12/2012 5:34:02 PMPNH
Arrived at the jobsite at 4:30- Gate locked, no access
FIR12-00332 INSP-Sprinkler Rough-in7/10/20127/12/20127/12/2012 5:32:25 PMPNR
This is an ug to cover. Richard is the contact.
Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
BLD12-00511 FIRE-Final Inspection7/12/20127/12/20127/12/2012 5:31:42 PMAPASS
Fire life safety finaled.
FIR09-00059 INSP-Final Inspection7/11/20127/12/20127/12/2012 5:30:29 PMAPASS
Fire alarm testing passed. Permit finaled.
FIR12-00284 INSP-Final Inspection7/11/20127/12/20127/12/2012 5:29:10 PMAPASS
Completed early morning alarm testing per contractor request. Inspection passed, permit finaled.
FIR12-00301 INSP-Final Inspection7/10/20127/12/20127/12/2012 5:26:37 PMAPASS
Fire sprinkler permit finaled. One missing escutcheon installed while on site.
FIR12-00039 INSP-Final Inspection7/11/20127/12/20127/12/2012 5:23:16 PMAPART
LCM cabinets finished with the exception of #5008 yet to be piped. 5000, 5001, 5003-07 and 5009 are complete.
FIR12-00210 INSP-Final Inspection7/11/20127/12/20127/12/2012 5:20:01 PMAPASS
Scope of work passed final inspection. Fire sprinkler permit finaled.
FIR12-00224 INSP-Final Inspection7/11/20127/12/20127/12/2012 5:18:43 PMAPASS
Fire sprinkler permit work passed final inspection.
FIR12-00039 INSP-Sprinkler Rough-in/Hydro7/11/20127/12/20127/12/2012 8:01:18 AMACANC
Phone #: ###-#### >> Inspection requested via web by John Wheeler Inspection cancelled from web by: John Wheeler