Inspections for the day of: Thursday, July 12, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00159 INSP-Final Inspection7/12/20127/12/20127/13/2012 12:59:40 PMPPASS
Permit finaled
FIR11-00543 INSP-Sprinkler Rough-in7/11/20127/12/20127/12/2012 3:57:17 PMPPASS
Lay-in tile can be installed. Overspaced heads will be verified later. Heads are overspaced in the Dressing Room. The 9' rule is being used off of two walls. Also the basement mechanical room needs to be resubmitted due to piping and head changes in the remote area.
BLD12-00827 FIRE-Final Inspection7/12/20127/12/20127/12/2012 3:49:38 PMPFAIL
Bill was not in the office when I was on site. Liz and I rescheduled for tomorrow.
BLD12-01667 FIRE-Final Inspection7/11/20127/12/20127/12/2012 3:46:45 PMPFAIL
Remove the manual flush bolts from in-active leaf of the main exit. See IFC 1008.1.9.4. Provide testing of the exit signs/emergency lights. Relocate or remove the exit sign at infilled door. Upright sprinkler heads exceed 130sq. ft. spacing at restrooms in warehouse. Provide and mount tagged fire extinguisher in normal path of travel as discussed.
FIR11-00651 INSP-Final Inspection7/11/20127/12/20127/12/2012 11:51:02 AMAPASS
Permit finaled. Forward flush passed.
FIR11-00651 INSP-Final Inspection7/12/20127/12/20127/12/2012 11:48:14 AMPPASS
Permit finaled
BLD11-02834 FIRE-Final Inspection7/11/20127/12/20127/12/2012 11:47:27 AMAPASS
Life safety passed
FIR12-00159 INSP-Alarm Testing7/11/20127/12/20127/12/2012 9:57:02 AMAFAIL
All times tested except there are issues with the duct smoke detectors. The first duct detector found and tested shut the hvac unit down but came in as the wrong zone. The second duct smoke detector found could not be tested due to the hvac unit not staying operational. The remaining two duct smoke detectors locations are not readily known nor is their controlling thermistats.
BLD12-01422 FIRE-Final Inspection7/11/20127/12/20127/12/2012 9:50:58 AMAPASS
life safety passed
FIR12-00334 INSP-Final Inspection7/11/20127/12/20127/12/2012 9:49:09 AMAPASS
Permit finaled