FIR12-00159
| INSP-Final Inspection | 7/12/2012 | 7/12/2012 | 7/13/2012 12:59:40 PM | P | PASS |
|
|
Permit finaled
|
FIR11-00543
| INSP-Sprinkler Rough-in | 7/11/2012 | 7/12/2012 | 7/12/2012 3:57:17 PM | P | PASS |
|
|
Lay-in tile can be installed. Overspaced heads will be verified later. Heads are overspaced in the Dressing Room. The 9' rule is being used off of two walls. Also the basement mechanical room needs to be resubmitted due to piping and head changes in the remote area.
|
BLD12-00827
| FIRE-Final Inspection | 7/12/2012 | 7/12/2012 | 7/12/2012 3:49:38 PM | P | FAIL |
|
|
Bill was not in the office when I was on site. Liz and I rescheduled for tomorrow.
|
BLD12-01667
| FIRE-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 3:46:45 PM | P | FAIL |
|
|
Remove the manual flush bolts from in-active leaf of the main exit. See IFC 1008.1.9.4. Provide testing of the exit signs/emergency lights. Relocate or remove the exit sign at infilled door. Upright sprinkler heads exceed 130sq. ft. spacing at restrooms in warehouse. Provide and mount tagged fire extinguisher in normal path of travel as discussed.
|
FIR11-00651
| INSP-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 11:51:02 AM | A | PASS |
|
|
Permit finaled. Forward flush passed.
|
FIR11-00651
| INSP-Final Inspection | 7/12/2012 | 7/12/2012 | 7/12/2012 11:48:14 AM | P | PASS |
|
|
Permit finaled
|
BLD11-02834
| FIRE-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 11:47:27 AM | A | PASS |
|
|
Life safety passed
|
FIR12-00159
| INSP-Alarm Testing | 7/11/2012 | 7/12/2012 | 7/12/2012 9:57:02 AM | A | FAIL |
|
|
All times tested except there are issues with the duct smoke detectors. The first duct detector found and tested shut the hvac unit down but came in as the wrong zone. The second duct smoke detector found could not be tested due to the hvac unit not staying operational. The remaining two duct smoke detectors locations are not readily known nor is their controlling thermistats.
|
BLD12-01422
| FIRE-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 9:50:58 AM | A | PASS |
|
|
life safety passed
|
FIR12-00334
| INSP-Final Inspection | 7/11/2012 | 7/12/2012 | 7/12/2012 9:49:09 AM | A | PASS |
|
|
Permit finaled
|