Inspections for the day of: Sunday, July 12, 2015.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00724 INSP-Alarm Testing7/12/20157/12/20157/12/2015 12:12:42 PMPPART
Initial testing of fire alarm system for the Jump building, including the Helix and A/G parking structure.
NOTE: U/G parking structure under permit # 13-00178.
Test included functional testing for all fire sprinkler systems (wet and dry) for all levels, and stairwells, including wet pipe water flows, dry pipe trip tests, low-air alarms, waterflows, tampers, etc. All systems tested OK. Some alarm descriptions need to be revised to reflect a better location of some of the systems. Simplex to make these changes, and wil confirm at the next inspection.
FIR14-00365 INSP-Alarm Testing7/12/20157/12/20157/12/2015 12:04:58 PMPPART
Test of dry pipe valves for 2nd and 3rd floor Helix structure, which includes ramp and some areas surrounding the ramp. Trip test of DP valves, including trip tests, low-air, waterflow and tampers. All tested OK
NOTE: Other systems protecting the Helix (floors 1 thru 6) have now been tested and passed. Kitchen and 2nd floor lobby on another permit.
FIR13-00178 INSP-Alarm Testing7/12/20157/12/20157/12/2015 11:59:58 AMPPART
test of fire sprinkler system for U/G parl'king garage, including four (4) dry pipe valves protecting the under ground parking garage and two (2) dry system suppling standpipes above the parking garage, including trip tests of the DP valves, low-air alarms, tampers and waterflows. All systems tested satisfactorily. Tom Walsh and Jim Page present for this inspection.