Inspections for the day of: Tuesday, July 12, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01778 ELE-Aging Inspection7/12/20167/12/20167/14/2016 8:09:10 AM CANC
ELE13-01214 ELE-Aging Inspection7/12/20167/12/20167/14/2016 8:08:14 AM CANC
ELE16-02223 Permanent Service7/12/20167/12/20167/12/2016 2:11:26 PMPPASS
Phone #: ###-#### Inspection requested via web by Don Conley
p/s u/g rec ok
ELE16-01750 Electrical Rough-In7/12/20167/12/20167/12/2016 1:33:16 PMPPASS
Robert. Wall cover kitchen area. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Kitchen area walls and ceiling rough in ok cover
ELE16-01582 Final7/11/20167/12/20167/12/2016 12:27:31 PMAPASS
Please call owner (Chris at ###-####) with at least 15 minutes notice so she can have it open.
Thanks, Barbara Phone #: ###-#### Inspection requested via web by Barbara Szurgot Kitchen and dining only. Final ok
ELE16-02207 Final7/11/20167/12/20167/12/2016 11:35:48 AMAPASS
John Phone #: ###-#### Final ok
ELE16-02207 Permanent Service7/12/20167/12/20167/12/2016 11:33:01 AMPPASS
John Phone #: 208-866-
Replaced triplex due to damage. p/s o/h rec ok
ELE16-02213 Electrical Rough-In7/12/20167/12/20167/12/2016 10:45:45 AMAFAIL
lock box is on hand rail code is 2323 Phone #: ###-#### Inspection requested via web by Jay Symonds
517.13- All receptacles located in patient care areas shall have metallic raceway installed as identified in 250.118. Alluminum flex shall not be installed in lengths exceeding 6' for effective fault path.
ELE15-02641 Electrical Rough-In7/11/20167/12/20167/12/2016 9:56:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
601 only drop lids rough in ok cover
ELE16-01838 Electrical Rough-In7/11/20167/12/20167/12/2016 9:34:46 AMAPASS
level 6 stack 2 ceiling inspection Phone #: ###-#### Inspection requested via web by Brandon Robinson
Level 6 stack 1 300.11- Low volt cables shall be supported independant of ceiling support system. Level 6 stack 2 ceiling and level 8 bathroom lids rough in ok cover