ELE13-02256
| DOC - Permit Finaled | 7/12/2017 | 7/12/2017 | 7/12/2017 2:53:32 PM | P | PASS |
|
|
Doc final ok
|
ELE12-01429
| ELE-Aging Inspection | 7/12/2017 | 7/12/2017 | 7/12/2017 2:44:16 PM | | FAIL |
|
|
Multiple attempts have gone unanswered. Waiting on contractor
|
ELE16-01838
| Final | 7/12/2017 | 7/12/2017 | 7/12/2017 2:38:07 PM | P | PASS |
|
|
Contact Tony for level 5 Lab 3 Autoclave hookups and sign off of project on hard card. Phone #: ###-#### Inspection requested via web by Tom Betty Final ok
|
ELE17-02224
| Electrical Rough-In | 7/12/2017 | 7/12/2017 | 7/12/2017 1:33:26 PM | P | FAIL |
|
|
Please see receptionist for access to TI space. Phone #: ###-#### Inspection requested via web by Lars Johnson 300.4- Where MC cable is run thru bored holes that do not maintain 1 1/4" from framing surface it shall be protected from physical damage. 314.23(B)- Boxes shall be rigidly mount in place. Kitchen 330.24- MC bending radius shall not damage cable. Kitchen area.
|
ELE17-02221
| Temporary Service | 7/12/2017 | 7/12/2017 | 7/12/2017 12:40:20 PM | P | PASS |
|
|
Temp Power Back yard Phone #: ###-#### Inspection requested via web by Charles Davis t/s o/h n ok
|
ELE17-00116
| Electrical Rough-In | 7/12/2017 | 7/12/2017 | 7/12/2017 12:39:50 PM | A | PASS |
|
|
Soffit Inspection on Level 1 in Wells Fargo. Contact Jon Novak Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Drop hardlids in each entance rough in ok cover
|
ELE17-02215
| Permanent Service | 7/11/2017 | 7/12/2017 | 7/12/2017 10:36:50 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kendra Lanham 1 ground rod in for service, length for 2nd to added when digging complete in area. p/s u/g n ok
|
ELE17-02218
| Rough-In Permanent Service | 7/11/2017 | 7/12/2017 | 7/12/2017 10:22:32 AM | A | PASS |
|
|
Call 30 min before you get there and I will meet you there. Thanks Phone #: ###-#### Inspection requested via web by Kevin Heideman Complete house rewire and new service. Rough in ok cover p/s o/h rec ok
|
ELE17-02209
| Permanent Service | 7/11/2017 | 7/12/2017 | 7/12/2017 9:57:15 AM | A | PASS |
|
|
service behind address at the shop Phone #: ###-#### Inspection requested via web by Kendra Lanham Facing service green building to left on other side of fence is being fed from this service, building to right is being demolished. p/s o/h n ok
|
ELE17-02184
| Rough-In Permanent Service | 7/11/2017 | 7/12/2017 | 7/12/2017 9:25:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough in ok cover p/s u/g n ok
|