ELE17-01935
| Electrical Rough-In | 7/12/2017 | 7/12/2017 | 7/12/2017 3:06:06 PM | P | PASS |
|
|
Underground Cover. Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen....
perrimeter unground and service stubs....ok
|
ELE16-03529
| Electrical Rough-In | 7/11/2017 | 7/12/2017 | 7/12/2017 1:39:39 PM | P | PASS |
|
|
Kitchen Phone #: ###-#### Inspection requested via web by Bryan Atkins...
full rough complete...areas marked on plans
|
ELE17-02208
| Final | 7/11/2017 | 7/12/2017 | 7/12/2017 12:56:06 PM | P | PASS |
|
|
Please call Dave at ###-#### for access before arrival. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell...
job complete...ok to final
|
ELE17-02208
| Electrical Rough-In | 7/12/2017 | 7/12/2017 | 7/12/2017 12:55:44 PM | P | PASS |
|
|
Please call Dave at ###-#### for access before arrival. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell...
new circuit ran from fuse panel in room to new water heater...sealtite flex with thhn wire, hot/cold bonded
|
ELE17-02222
| Temporary Service | 7/12/2017 | 7/12/2017 | 7/12/2017 12:14:28 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn....
t/s u/g n ok
|
ELE17-01504
| Final | 7/11/2017 | 7/12/2017 | 7/12/2017 11:58:19 AM | A | PASS |
|
|
AM requested. Please call Lynn at ###-####. Phone #: ###-#### Inspection requested via web by Lynn Proctor...
ok to final
|
ELE17-01002
| Conference | 7/11/2017 | 7/12/2017 | 7/12/2017 10:29:39 AM | A | PASS |
|
|
John Phone #: ###-####...
discussed what needed for relocation of service and rewiring of sub panels....wire protection, temporary location of sub panel for access to lift roof and keep power to house, homeowner capable of work
|
ELE17-01529
| Final | 7/12/2017 | 7/12/2017 | 7/12/2017 9:24:44 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn...
ok to final
|
ELE17-02148
| Rough-In Permanent Service | 7/11/2017 | 7/12/2017 | 7/12/2017 9:02:47 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn...
rough ok to cover p/s u/g n ok
|
ELE17-01411
| Permanent Service | 7/11/2017 | 7/12/2017 | 7/12/2017 8:36:20 AM | A | FAIL |
|
|
Call Corey @ ###-#### Phone #: ###-#### Inspection requested via web by Seth Stears...
1) available fault current labelling needs installed
2) open holes in panels need to be sealed
|