Inspections for the day of: Wednesday, July 12, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01935 Electrical Rough-In7/12/20177/12/20177/12/2017 3:06:06 PMPPASS
Underground Cover. Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen....

perrimeter unground and service stubs....ok
ELE16-03529 Electrical Rough-In7/11/20177/12/20177/12/2017 1:39:39 PMPPASS
Kitchen Phone #: ###-#### Inspection requested via web by Bryan Atkins...

full rough complete...areas marked on plans
ELE17-02208 Final7/11/20177/12/20177/12/2017 12:56:06 PMPPASS
Please call Dave at ###-#### for access before arrival. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell...

job complete...ok to final
ELE17-02208 Electrical Rough-In7/12/20177/12/20177/12/2017 12:55:44 PMPPASS
Please call Dave at ###-#### for access before arrival. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell...

new circuit ran from fuse panel in room to new water heater...sealtite flex with thhn wire, hot/cold bonded
ELE17-02222 Temporary Service7/12/20177/12/20177/12/2017 12:14:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn....

t/s u/g n ok
ELE17-01504 Final7/11/20177/12/20177/12/2017 11:58:19 AMAPASS
AM requested. Please call Lynn at ###-####. Phone #: ###-#### Inspection requested via web by Lynn Proctor...

ok to final
ELE17-01002 Conference7/11/20177/12/20177/12/2017 10:29:39 AMAPASS
John Phone #: ###-####...

discussed what needed for relocation of service and rewiring of sub panels....wire protection, temporary location of sub panel for access to lift roof and keep power to house, homeowner capable of work
ELE17-01529 Final7/12/20177/12/20177/12/2017 9:24:44 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn...

ok to final
ELE17-02148 Rough-In Permanent Service7/11/20177/12/20177/12/2017 9:02:47 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...

rough ok to cover
p/s u/g n ok
ELE17-01411 Permanent Service7/11/20177/12/20177/12/2017 8:36:20 AMAFAIL
Call Corey @ ###-#### Phone #: ###-#### Inspection requested via web by Seth Stears...

1) available fault current labelling needs installed

2) open holes in panels need to be sealed