FIR18-00187
| INSP-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 1:15:53 PM | P | CANC |
|
|
On order for water supply to fire sprinklers scheduled for 13JULY2018, final inspection for overhead fire sprinklers will be completed then. This request is cancelled.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00068
| INSP-Final Inspection | 7/12/2018 | 7/12/2018 | 7/12/2018 12:54:24 PM | P | PASS |
|
|
Final inspection for undergorund supply complete.
|
FIR18-00068
| INSP-Sprinkler Rough-in/Hydro | 7/11/2018 | 7/12/2018 | 7/12/2018 12:53:04 PM | A | DONE |
|
|
Hydrostatic test for underground supply witnessed, no pressure loss observed at riser provided gauge.
underground hydro Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
BLD18-02297
| FIRE-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 11:35:28 AM | A | CANC |
|
|
Point of contact was not available, left a message on voicemail to contact me before 1130, did not recieve a call by 1130, inspection request will need to be rescheduled, this request is cancelled.
Dale Phone #: ###-####
|
BLD17-03614
| FIRE-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 11:08:05 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Philip Allen Inspection cancelled from web by: Philip Allen
|
FIR18-00356
| INSP-Sprinkler Rough-in | 7/11/2018 | 7/12/2018 | 7/12/2018 11:03:47 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings areas approved for cover.
ROY NELSON Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
FIR18-00196
| INSP-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 11:02:51 AM | A | PASS |
|
|
Final fire alarm inspection complete.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
FIR18-00068
| INSP-Supply line flush | 7/11/2018 | 7/12/2018 | 7/12/2018 10:48:10 AM | A | DONE |
|
|
Undergorund main line flush complete.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
BLD18-02375
| FIRE-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 10:03:47 AM | A | FAIL |
|
|
Provide fire extinguisher with a current inspection tag. Provide sticker on the interior of the main entry reading "Door to remain unlocked while occupied'.
Joe-please call with an approx time so they can meet you and let you in Phone #: ###-####
|
FIR18-00297
| INSP-Sprinkler Rough-in | 7/12/2018 | 7/12/2018 | 7/12/2018 8:43:27 AM | P | PART |
|
|
Final fire sprinkler inspection for area of work complete. FIR permit will remain in issued status until core and shell permits are complete.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00454
| INSP-Sprinkler Rough-in | 7/11/2018 | 7/12/2018 | 7/12/2018 8:18:17 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|