Inspections for the day of: Friday, July 12, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02372 Conference7/11/20197/12/20197/12/2019 2:35:33 PMPDONE
Contact: Brian Gee Phone #: ###-#### Inspection requested via web by Deb Gooden Discussed early AM saw cut behind building in a high traffic area. Will make 1st stop 7/15/19 to see if ready. Photos will be ok if time gets tight.
ELE19-02509 Permanent Service7/11/20197/12/20197/12/2019 1:59:41 PMPPASS
This request is for an inspection for a panel upgrade from 125 amps to 200 amps. Please call Darryn ###-#### with any questions. Thank You!! Phone #: ###-#### Inspection requested via web by Darryn Coburn p/s o/h rec ok
ELE19-02456 Permanent Service7/10/20197/12/20197/12/2019 1:13:36 PMPPASS
Call Fred with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Clayton Morgan p/s o/h rec ok
ELE19-02585 Final7/12/20197/12/20197/12/2019 12:43:27 PMPFAIL
Phone #: ###-#### Inspection requested via web by Steven Ragan 110.26D Illumination shall be provided around all service equipment
ELE19-02585 Electrical Rough-In7/12/20197/12/20197/12/2019 12:42:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Steven Ragan Small section of underground ok to cover
ELE19-01016 Permanent Service7/12/20197/12/20197/12/2019 12:40:29 PMPPASS
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack p/s u/g n ok
ELE19-00910 Conference7/11/20197/12/20197/12/2019 11:52:13 AMADONE
Disconnecting means of chillers with line side controller and load side VFD on opposite sides of units and out of site from VFD''s. Phone #: ###-#### Inspection requested via web by Tom Betty As long as Disc. is lockable, location ok.
ELE19-02559 Final7/10/20197/12/20197/12/2019 11:48:25 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rob Maes 110.26 Working space shall be 30in wide and 36in deep
ELE19-01443 Final7/12/20197/12/20197/12/2019 11:17:47 AMAPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE19-01424 Electrical Rough-In7/11/20197/12/20197/12/2019 10:42:42 AMAPASS
Contact Scott for underground conduit from receptacle location to fountain pump. Phone #: ###-#### Inspection requested via web by Tom Betty UG ok to cover
ELE19-02540 Rough-In Permanent Service7/11/20197/12/20197/12/2019 10:42:17 AMAPASS
Please contact when done Phone #: ###-#### Inspection requested via web by Thomas wilson UG ok p/s u/g n ok
ELE19-02087 Electrical Rough-In7/11/20197/12/20197/12/2019 9:39:22 AMAPASS
Wall rough-in, Chad Vanorden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Talked about Existing House panel and Meter Base in main electrical room. Top breaker is at 7ft and meter base has Cardboard blank. Both items need addressed. Discussed cleaning up old electrical and removing any violations in work areas. Misc walls in breakroom and front office area ok to cover.
ELE19-02106 Electrical Rough-In7/11/20197/12/20197/12/2019 8:06:04 AMAPASS
Ceiling grid Phone #: ###-#### Inspection requested via web by Jim Williams Ceilings only ok to cover