BLD17-02871
| FIRE-Conference | 7/12/2019 | 7/12/2019 | 7/12/2019 1:14:41 PM | P | DONE |
|
|
I went over the exit sign/emergency lights as shown on the city approved plans that are missing. We also went over the requirements for the one hour fire sprinkler riser room.
|
FIR18-00435
| INSP-Final Inspection | 7/11/2019 | 7/12/2019 | 7/12/2019 1:07:27 PM | P | PASS |
|
|
Permit finaled
Josh Eaton is the contact for this final inspection. We appreciate your help with this. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00503
| INSP-Alarm Testing | 7/11/2019 | 7/12/2019 | 7/12/2019 11:12:45 AM | A | DONE |
|
|
Todays inspection we verified phone lines, panel, duct detector/hvac unit shutdown, flow switches and tamper switches. Plan modifications are needed showing all of the changes. Strobes are over spaced and need to be relocated or the candella adjusted. Smoke detectors are too close to diffusers. Strobes are missing in on location on the second floor as marked on the plans. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00435
| INSP-Final Inspection | 7/10/2019 | 7/12/2019 | 7/11/2019 3:42:18 PM | P | CANC |
|
|
Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|