Inspections for the day of: Wednesday, July 13, 2005.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01581 Electrical Rough-In7/13/20057/13/20057/13/2005 4:19:09 PMPCANC
Ceiling cover re-inspect, please contact Tom, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy WatersROT
ELE05-02501 Permanent Service7/13/20057/13/20057/13/2005 4:16:53 PMPCANC
ron ###-####
ROT called contractor
ELE05-02498 Electrical Rough-In7/13/20057/13/20057/13/2005 4:14:33 PMPCANC
###-#### - george
rot
ELE05-02401 Final7/13/20057/13/20057/13/2005 4:12:14 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
ELE05-02337 Temporary Service7/12/20057/13/20057/13/2005 4:11:56 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: William Zerfas
Connect GEC to neutral
fitting required for GEC
ELE05-00974 Final7/12/20057/13/20057/13/2005 3:16:47 PMAFAIL
heather; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
210.8 Ground-Fault Circuit-Interrupter Protection for Personnel.
(A) Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in (1) through (8) shall have ground-fault circuit-interrupter protection for personnel.
(1) Bathrooms
(2) Garages

408.4 Circuit Directory or Circuit Identification
Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include sufficient detail to allow each circuit to be distinguished from all others. The identification shall be included in a circuit directory that is located on the face or inside of the panel door in the case of a panelboard, and located at each switch on a switchboard.

406.4 Receptacle Mounting.
(A) Boxes That Are Set Back. Receptacles mounted in boxes that are set back of the wall surface, as permitted in 370.20, shall be installed so that the mounting yoke or strap of the receptacle is held rigidly at the surface of the wall.
(D) Position of Receptacle Faces. After installation, receptacle faces shall be flush with or project from faceplates of insulating material and shall project a minimum of 0.4 mm (0.015 in.) from metal faceplates.

ELE05-02479 Electrical Rough-In7/12/20057/13/20057/13/2005 2:38:29 PMAPASS
One time inspection, your office has a fax of work site. Any questions for the electrician call Fred ###-####; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
ELE05-02438 Final7/13/20057/13/20057/13/2005 2:09:44 PMPPART
Ready for Rough In inspection. Please inspect Early afternoon. It would be greatly appreciated. ; Phone #: ###-#### Internet Inspection Request from: BRIAN
KEITH
kitchen and laundry ok
ELE05-02496 Electrical Rough-In7/13/20057/13/20057/13/2005 1:37:36 PMPPASS
###-#### rough-in walls & cielings; Phone #: ###-#### Internet Inspection Request from: Nikki Day
ELE05-02332 Temporary Service7/12/20057/13/20057/13/2005 12:12:36 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: William Zerfas
GEC to neutral and fitting required on
GEC
ELE05-01727 Final7/13/20057/13/20057/13/2005 10:06:38 AMAPASS
Scheduled by a contractor via Hello! on 7/13/2005 at 6:46:17 AM. Contact: ###-####.
ELE05-02173 Electrical Rough-In7/12/20057/13/20057/13/2005 9:48:28 AMAPART
Scheduled by a contractor via Hello! on 7/12/2005 at 7:26:37 PM. Contact: ###-####.
checked 1 lighr fixture
ELE05-02000 Final7/12/20057/13/20057/13/2005 9:22:01 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
ELE05-01581 Electrical Rough-In7/12/20057/13/20057/13/2005 9:03:02 AMAFAIL
ceiling cover rough-in, please contact Tom, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters
supports for mc and raceways above ceiling 3rd floor
ELE03-02916 Final7/12/20057/13/20057/13/2005 8:38:19 AMAPASS
8:30am????///lynn ; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
ELE05-01422 Electrical Rough-In7/12/20057/13/20057/13/2005 8:16:03 AMAPASS
Ceiling cover re-inspection, please contact Dan (Gary onsite) thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters
ELE05-02479 Permanent Service7/13/20057/13/20057/13/2005 12:00:00 AMPPASS
One time inspection, your office has a fax of work site. Any questions for the electrician call Fred ###-####; Phone #: ###-#### Internet Inspection Request from: BRIAN
KEITH
P/S U/G N Ok