Inspections for the day of: Wednesday, July 13, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00775 FIRE-Conference7/12/20057/13/20057/13/2005 4:13:00 PMPCANC
Cancel inspection per Pat the GC, he will re-schedule the confrence at a later date.
BLD05-00481 FIRE-Final Inspection7/12/20057/13/20057/13/2005 3:04:53 PMPFAIL
Remove thumbturn and supply approved door hardware at both main entry/exit doors, provide fire ext. with current annual inspection tag installed with handle no higher than 48" AFF, provide suite address at main entrance.
FIR05-00372 INSP-Sprinkler Rough-in7/12/20057/13/20057/13/2005 1:49:36 PMPCANC
CONTACT MATT, R-IN. AFTER 3PM; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
BLD05-00946 FIRE-Final Inspection7/13/20057/13/20057/13/2005 1:01:42 PMPFAIL
Repair emergency light/exit sign at back door, test HVAC duct smoke detection devices, provide proper verbage on sign above door at main entry/exit, provide annual inspection tags on fire extinguishers, repair two exit signs at main entry, repair main exit discharge light.
MIS05-00103 FIR-Final7/12/20057/13/20057/13/2005 10:02:03 AMAPASS
Fire life safety passed inspection.
FIR05-00350 INSP-Final Inspection7/12/20057/13/20057/13/2005 9:29:38 AMAPASS
Fire sprinkler permit finaled.
FIR05-00372 INSP-Sprinkler Rough-in7/12/20057/13/20057/12/2005 2:36:56 PMPCANC
CONTACT MATT. R-IN.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley