Inspections for the day of: Thursday, July 13, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00481 INSP-Sprinkler Rough-in7/13/20067/13/20067/13/2006 3:59:24 PMPPASS
Rough-in inspection passed.
FIR06-00484 INSP-Final Inspection7/13/20067/13/20067/13/2006 3:57:47 PMPPASS
Permit finaled.
FIR06-00392 INSP-Final Inspection7/13/20067/13/20067/13/2006 2:40:02 PMPPASS
Sprinkler permit finaled
FIR06-00439 INSP-Sprinkler Rough-in7/12/20067/13/20067/13/2006 2:13:39 PMAPASS
Sprinkler piping is ok to cover.
BLD05-02650 FIRE-Final Inspection7/13/20067/13/20067/13/2006 1:59:58 PMPFAIL
Exit discharge lights did not work.
FIR05-00854 INSP-Final Inspection7/12/20067/13/20067/13/2006 1:11:21 PMACANC
James said he is not ready.
FIR06-00187 FIR-Aging Inspection7/13/20067/13/20067/13/2006 1:06:29 PM NR
Work is in progress
BLD06-00687 FIRE-Final Inspection7/12/20067/13/20067/13/2006 1:05:05 PMPFAIL
Life safety was not ready for inspection due to inoperative exit signs and emergency lights. Also fire extinguishers need addressed. I went over life safety requirements with contractor.
FIR06-00246 INSP-Alarm Testing7/12/20067/13/20067/13/2006 12:22:52 PMPPASS
Permit finaled
FIR06-00198 INSP-Final Inspection7/12/20067/13/20067/13/2006 12:22:29 PMAFAIL
Corrections as noted on the previous inspection have been taken care of but the contractor did not have the approved plans on site so that the inspection could be continued.
FIR05-00880 INSP-Final Inspection7/12/20067/13/20067/13/2006 11:06:18 AMPFAIL
Need print out of the signals sent and updated plans showing the additional tamper switches.
FIR05-00659 INSP-Final Inspection7/13/20067/13/20067/13/2006 11:05:43 AMPFAIL
Fire sprinkler work is not finished yet and updated plans are required.
BLD05-00775 FIRE-Final Inspection7/12/20067/13/20067/13/2006 11:05:10 AMPFAIL
Life safety is not ready yet since emergency lighting and other permits have not been finaled
BLD06-00400 FIRE-Final Inspection7/12/20067/13/20067/13/2006 8:56:51 AMAPASS
Life safety finaled
FIR06-00182 INSP-Alarm Testing7/7/20067/13/20067/13/2006 8:54:25 AMAFAIL
Remove the a/v in the gas chamber. The a/v on the wall immediately outside of the chamber provides adequate coverage. Retest circuit after this removal at final.
FIR06-00304 INSP-Final Inspection7/7/20067/13/20067/13/2006 8:53:06 AMAPASS
Permit finaled
FIR06-00308 INSP-Final Inspection7/7/20067/13/20067/13/2006 8:52:42 AMAPASS
Permit finaled