Inspections for the day of: Wednesday, July 13, 2016.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01800 ELE-Aging Inspection7/13/20167/13/20167/14/2016 8:11:34 AM CANC
ELE10-01289 ELE-Aging Inspection7/13/20167/13/20167/14/2016 8:10:30 AM CANC
ELE16-00867 Final7/13/20167/13/20167/13/2016 3:50:06 PMPFAIL
Ben Phone #: ###-####
210.8- Receptacles located with in 6' of a sink shall have GFCI protection. Bar area and near water heater.
Critical systems related to core and shall be operational prior to final.
ELE15-00495 Electrical Rough-In7/13/20167/13/20167/13/2016 3:49:19 PMPPASS
Ceiling cover inspection retail bathrooms first floor. Contact is Eric Gibson ###-####. Phone #: ###-#### Inspection requested via web by Toby Groves
Retail B bath hardlids Rough in ok cover
ELE16-02238 Final7/13/20167/13/20167/13/2016 3:48:29 PMPPASS
Larry Looney is contact. Newly installed pole with .2A repeater and antenna to be direct wired to Idaho Power. Phone #: ###-#### Inspection requested via web by Clint Tate
Antenna and repeater 20'+ on pole to be powered by Idaho Power without meter or service. Discussed fuse and disconnecting means for servicing. Will discuss with Daryl DeGrange when he returns from leave. Devices for gas company to monitor gas meters. Final ok
ELE15-03901 Electrical Rough-In7/13/20167/13/20167/13/2016 3:21:10 PMPPASS
7th floor grid ceiling inspection and transformer inspection in penthouse mechanical room. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Areas noted in book on 7th and transformer on penthouse level rough in ok cover
ELE16-02240 Final7/13/20167/13/20167/13/2016 12:55:59 PMPCANC
Phone #: ###-#### Inspection requested via web by Dan Rohl Needed temp service inspection
ELE16-02240 Temporary Service7/13/20167/13/20167/13/2016 12:55:23 PMPPASS
Phone #: ###-#### Inspection requested via web by Dan Rohl t/s u/g n ok
ELE16-01659 Final7/13/20167/13/20167/13/2016 11:29:28 AMPCANC
I should be able to be there after 3:00 PM. No one else will be home, but the front door is unlocked and the owner has approved entry for the inspection. The entire front area of the home is not occupied during remodel. I''ll call this afternoon when I can meet at the home and if the timing works great, if not I''d appreciate the inspection on the Kitchen final. Phone #: ###-#### Inspection requested via web by JOHN MCCURDY
Contractor called asked to cancel and reschedule for next day
ELE15-01348 Electrical Rough-In7/13/20167/13/20167/13/2016 11:28:20 AMPPASS
Level 1 of Annex exterior soffit overhead. Phone #: ###-#### Inspection requested via web by Brandon Robinson
Annex level 1 south soffit rough in ok cover
ELE14-03316 Electrical Rough-In7/13/20167/13/20167/13/2016 11:15:23 AMAPASS
Garage expansion room OB-G120 future concierge Phone #: ###-#### Inspection requested via web by Tom Betty
Walls and insulate lid at area noted. Rough in ok cover.
ELE16-00089 Electrical Rough-In7/13/20167/13/20167/13/2016 10:27:08 AMAPASS
Call Bob for r/i inspection of walls on 4th floor level area C and D, partial only. Phone #: ###-#### Inspection requested via web by Rafael Castillo
4th floor bath and stair 3 wall as marked in book rough in ok cover
ELE16-01596 Final7/12/20167/13/20167/13/2016 9:43:11 AMAPASS
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey
Final ok
ELE16-02149 Permanent Service7/11/20167/13/20167/13/2016 9:04:18 AMAPASS
New service going up next to old one. Will schedule final after change-over is done. Will be converting existing fuse panel into j-box, and run new grounded circuits to Dryer, water heater, washer, and AC.
If inside access is needed, back door should be unlocked. Phone #: ###-#### Inspection requested via web by Troy Cobb
p/s o/h rec ok
ELE16-02220 Final7/12/20167/13/20167/13/2016 8:49:18 AMAPASS
Phone #: ###-#### Inspection requested via web by Charmel Kubik
Final ok
ELE16-02218 Final7/12/20167/13/20167/13/2016 8:48:44 AMAPASS
Phone #: ###-#### Inspection requested via web by Charmel Kubik
Final ok
ELE16-02219 Final7/12/20167/13/20167/13/2016 8:48:13 AMAPASS
Phone #: ###-#### Inspection requested via web by Charmel Kubik
Final ok