Inspections for the day of: Wednesday, July 13, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-02185 Electrical Rough-In7/13/20167/13/20167/13/2016 1:57:17 PMPFAIL
call Josh for access Phone #: ###-#### 110.12 A. Unused openings shall be closed. Garage sub panel 300.4 A 1, NM Cable through bored holes less than 1 1/4in from face of framing member shall be protected Up bath/ down bed ceiling.
ELE16-01553 Permanent Service7/13/20167/13/20167/13/2016 1:12:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Jim Williams p/s o/h rec ok
ELE16-01183 Electrical Rough-In7/13/20167/13/20167/13/2016 12:48:30 PMPPASS
For access please call Johnathon 1/2 hr prior to inspection. ###-####.

Phone #: ###-#### Inspection requested via web by Terry Scott Kitchen countertop heat. Ok to cover
ELE15-03463 Final7/13/20167/13/20167/13/2016 12:15:39 PMPFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI 680.12 Disconnect shall be outside of 5ft from waters edge, Hot tub.c 680.34 Recepticle shall be outside of 6ft from waters edge. Hot tub. Pantry outlets dont work
ELE16-02126 Electrical Rough-In7/12/20167/13/20167/13/2016 10:49:53 AMAPASS
Rough in inspection for OK to cover. Phone #: ###-#### Inspection requested via web by Kendra Lanham Partial cover only, All 2nd floor. 1st floor no Utility room, Basement no east room.
ELE16-02233 Electrical Rough-In7/13/20167/13/20167/13/2016 10:05:47 AMAFAIL
Someone should be on site all morning. Any questions please call Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman 210.52 C 4. Outlet within 24 in of sink
ELE16-00416 Electrical Rough-In7/12/20167/13/20167/13/2016 9:41:42 AMAFAIL
Todd Phone #: ###-#### Electrical contractor doing work without permit. Was instructed to pull Contractors permit. Homeowner pulled permit but did not do the wiring
ELE16-02229 Temporary Service7/13/20167/13/20167/13/2016 9:33:54 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Zane Robertson Inspection cancelled from web by: Zane Robertson