Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00406 INSP-Sprinkler Rough-in7/13/20167/13/20167/13/2016 2:53:06 PMPPART
Todays inspection was just for the stub out from the building. Top of pipe measured 4'-2" to the top of the footing. Per the job superintendant and the underground installer an additional 12" of dirt is to be installed on top of the pipe. This will give the required 4'-6" of cover.
BLD13-00166 FIRE-Conference7/13/20167/13/20167/13/2016 2:40:16 PMPDONE
I stopped and tried to perform another inspection but the owner was not there and due to business operations could not re-verify corrections. I have re-scheduled my self for a follow up inspection.
FIR15-00709 INSP-Sprinkler Rough-in7/12/20167/13/20167/13/2016 2:29:59 PMPPASS
See the city approved plans for location of pendant sprinkler heads that are ok to cover today. Conference room/adjoining room.
BLD16-00576 FIRE-Alarm Testing7/13/20167/13/20167/13/2016 1:46:21 PMPPART
Intent was to test the smoke evacuation system but it appears to be wired incorrectly. Exit signs and emergency lighting functioned correctly.
BLD16-01797 FIRE-Conference7/13/20167/13/20167/13/2016 1:42:00 PMPDONE
The project superintendant and I went over life safety requirements. I suggested that he employ a fire alarm contractor to see if the existing fire alarm system needs to be extended into the remodel area.
FIR16-00448 INSP-Sprinkler Rough-in7/13/20167/13/20167/13/2016 1:39:04 PMPPASS
Rough-in passed. Piping can be covered.
BLD16-01813 FIRE-Final Inspection7/12/20167/13/20167/13/2016 10:59:06 AMPFAIL
Life safety can be finaled when the project related fire sprinkler permit is finaled.
FIR16-00339 INSP-Final Inspection7/12/20167/13/20167/13/2016 10:26:10 AMAFAIL
Not all of the tile is installed and two pendant heads have the shipping caps still on.
BLD06-02323 FIRE-Final Inspection7/12/20167/13/20167/13/2016 9:05:43 AMAPASS
Life safety passed
FIR16-00419 INSP-Final Inspection7/12/20167/13/20167/13/2016 8:52:29 AMACANC
Jim Danes is contact. Please let him know at least half an hour in advance of inspection so he can be there if needed. Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
FIR16-00419 INSP-Sprinkler Rough-in7/12/20167/13/20167/13/2016 8:29:55 AMAFAIL
A single pendant head located above the cooler has not been installed per plan which made it overspaced. All other work looks ok and piping can be covered.