FIR16-00406
| INSP-Sprinkler Rough-in | 7/13/2016 | 7/13/2016 | 7/13/2016 2:53:06 PM | P | PART |
|
|
Todays inspection was just for the stub out from the building. Top of pipe measured 4'-2" to the top of the footing. Per the job superintendant and the underground installer an additional 12" of dirt is to be installed on top of the pipe. This will give the required 4'-6" of cover.
|
BLD13-00166
| FIRE-Conference | 7/13/2016 | 7/13/2016 | 7/13/2016 2:40:16 PM | P | DONE |
|
|
I stopped and tried to perform another inspection but the owner was not there and due to business operations could not re-verify corrections. I have re-scheduled my self for a follow up inspection.
|
FIR15-00709
| INSP-Sprinkler Rough-in | 7/12/2016 | 7/13/2016 | 7/13/2016 2:29:59 PM | P | PASS |
|
|
See the city approved plans for location of pendant sprinkler heads that are ok to cover today. Conference room/adjoining room.
|
BLD16-00576
| FIRE-Alarm Testing | 7/13/2016 | 7/13/2016 | 7/13/2016 1:46:21 PM | P | PART |
|
|
Intent was to test the smoke evacuation system but it appears to be wired incorrectly. Exit signs and emergency lighting functioned correctly.
|
BLD16-01797
| FIRE-Conference | 7/13/2016 | 7/13/2016 | 7/13/2016 1:42:00 PM | P | DONE |
|
|
The project superintendant and I went over life safety requirements. I suggested that he employ a fire alarm contractor to see if the existing fire alarm system needs to be extended into the remodel area.
|
FIR16-00448
| INSP-Sprinkler Rough-in | 7/13/2016 | 7/13/2016 | 7/13/2016 1:39:04 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
BLD16-01813
| FIRE-Final Inspection | 7/12/2016 | 7/13/2016 | 7/13/2016 10:59:06 AM | P | FAIL |
|
|
Life safety can be finaled when the project related fire sprinkler permit is finaled.
|
FIR16-00339
| INSP-Final Inspection | 7/12/2016 | 7/13/2016 | 7/13/2016 10:26:10 AM | A | FAIL |
|
|
Not all of the tile is installed and two pendant heads have the shipping caps still on.
|
BLD06-02323
| FIRE-Final Inspection | 7/12/2016 | 7/13/2016 | 7/13/2016 9:05:43 AM | A | PASS |
|
|
Life safety passed
|
FIR16-00419
| INSP-Final Inspection | 7/12/2016 | 7/13/2016 | 7/13/2016 8:52:29 AM | A | CANC |
|
|
Jim Danes is contact. Please let him know at least half an hour in advance of inspection so he can be there if needed. Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
|
FIR16-00419
| INSP-Sprinkler Rough-in | 7/12/2016 | 7/13/2016 | 7/13/2016 8:29:55 AM | A | FAIL |
|
|
A single pendant head located above the cooler has not been installed per plan which made it overspaced. All other work looks ok and piping can be covered.
|