Inspections for the day of: Wednesday, July 13, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-01680 FIRE-Conference7/12/20167/13/20167/13/2016 2:38:31 PMPDONE
Fire conference complete.
FIR16-00040 INSP-Sprinkler Rough-in/Hydro7/13/20167/13/20167/13/2016 2:12:56 PMPPART
Partial rough to cover inspection complete for underground main supply located on southside of jobsite, partial cover is approved for underground supply running from west to east on southside of project, change of direction where main turns to go into building will be inspected at later date.
FIR16-00305 INSP-Sprinkler Rough-in7/13/20167/13/20167/13/2016 1:51:53 PMPPART
Partial rough to cover complete for level 2 overhead fire sprinkler piping, notated the city approved drawings with blue highlighter/red ink, the overhead fire sprinkler piping approved for cover.
FIR15-00809 INSP-Sprinkler Rough-in7/12/20167/13/20167/13/2016 9:59:16 AMPCANC
Not ready for rough in inspection for overhead sprinkler piping for level 3, area's on level 3 missing tenting insulation, insulation needs to be completely installed for rough in inspection for cover to be approved.
FIR15-00809 INSP-Sprinkler Rough-in/Hydro7/12/20167/13/20167/13/2016 9:56:45 AMPPASS
Hydrostatic test for overhead fire sprinkler piping complete for level 3, overhead fire sprinkler hydrostaic test for this building complete.
FIR16-00275 INSP-Sprinkler Rough-in/Hydro7/12/20167/13/20167/13/2016 9:19:33 AMPDONE
Rough to cover inspection for overhead fire sprinklers complete for level 6 as well as overhead fire sprinkler hydrostatic test for level 6.
FIR16-00008 INSP-Sprinkler Rough-in/Hydro7/12/20167/13/20167/13/2016 9:17:56 AMPDONE
Notes entered into FIR15-00602 for overhead sprinkler hydrostatic test completed on levels 1 and 2 of annex building.
FIR15-00602 INSP-Sprinkler Rough-in/Hydro7/12/20167/13/20167/13/2016 9:12:54 AMPPASS
Hydrostatic test for overhead fire sprinkler piping on levels 1 and 2 complete.
BLD14-02800 FIRE-Final Inspection7/11/20167/13/20167/13/2016 9:11:38 AMAPASS
FInal life fire safety inspection passed/complete.
BLD15-04479 FIRE-Final Inspection7/12/20167/13/20167/13/2016 9:10:46 AMAPASS
Previously noted issue with fire sprinklers repaired, fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers in common area's with current inspection tags. Final life fire safety inspection passed/complete.