ELE18-01533
| Electrical Rough-In | 7/13/2018 | 7/13/2018 | 7/13/2018 2:36:41 PM | P | PART |
|
|
Ceiling cover. Phone #: ###-#### Inspection requested via web by Buster Bowen Areas not accessible due to wet glue conference rooms 2, 3, file room, offices 10, 11, 37. Corridors not ready. Rest of interior offices grid rough in ok cover
|
ELE18-02642
| Electrical Rough-In | 7/13/2018 | 7/13/2018 | 7/13/2018 2:14:46 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Main level dividing wall rough in ok cover
|
ELE17-02862
| Electrical Rough-In | 7/13/2018 | 7/13/2018 | 7/13/2018 1:32:30 PM | P | PASS |
|
|
units 209 , 210 , 211 , 216 , 215 and drop ceilings 510 , 511 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Discussed location of HVAC disconnects for mini split unit located 10' above grade. Fused disconnects require minimum work space due to servicing fuses. Non fused disconnects do not require work space. Rooms and hard lids noted rough in ok cover
|
ELE18-02558
| Temporary Service | 7/13/2018 | 7/13/2018 | 7/13/2018 12:31:00 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman t/s o/h n ok
|
ELE18-01910
| Electrical Rough-In | 7/12/2018 | 7/13/2018 | 7/13/2018 11:39:03 AM | A | PASS |
|
|
Job Foreman: Jay Karel Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Listing and disconnecting means confirmed. Rough in ok
|
ELE18-01910
| Final | 7/13/2018 | 7/13/2018 | 7/13/2018 11:38:45 AM | P | PASS |
|
|
Job Foreman: Jay Karel Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Final ok
|
ELE18-01775
| Electrical Rough-In | 7/12/2018 | 7/13/2018 | 7/13/2018 9:48:57 AM | A | PASS |
|
|
EQ bonding plane wiring ; connections, handrail sleeves, handicap lift Phone #: ###-#### Inspection requested via web by Lars Johnson Potting not complete, EQ plane, hand rails at each stair location and handicap base bond rough in ok cover
|
ELE18-02032
| Electrical Rough-In | 7/12/2018 | 7/13/2018 | 7/13/2018 9:00:31 AM | A | PASS |
|
|
second floor new ceiling soffit cover inspection. Phone #: ###-#### Inspection requested via web by Jim Noll Level 2 soffits on Main east of 8th, from Main to Idaho on 8th and on Idaho east of 8th rough in ok cover.
|