Inspections for the day of: Wednesday, July 14, 2004.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00227 FIR-Aging Inspection7/14/20047/14/20047/14/2004 12:00:00 AM NR
Per the fire sprinkler contractor the work is done and an inspection will be called in. 7/14/2004 1:31:47 PM
FIR04-00402 INSP-Final Inspection7/13/20047/14/20047/14/2004 12:00:00 AMAFAIL
Can't give final since no ceiling tile has been installed and one existing hanger ring needs to be re-attached to the building structure. See approved plans for location. 7/14/2004 9:56:38 AM
FIR04-00304 INSP-Final Inspection7/13/20047/14/20047/14/2004 12:00:00 AMAFAIL
Provide knox key box per review note #7. Provide signage per review note#8. Provide complete map for the facp. Repair the exterior access doors to the fire alarm panel room 7/14/2004 10:01:51 AM
BLD03-01726 FIRE-Final Inspection7/14/20047/14/20047/14/2004 12:00:00 AMPFAIL
Provide building address and suite numbers. Provide door hardware for compliance verification. Provide "Door to remain unlocked..." sticker on the tenant exit. Provide approved door hardware on the rear doors. Key locking as provided is not allowed. Provide a fire extinguisher per review notes. Provide panic hardware on the main exit. Install and test exit sign. 7/14/2004 4:04:31 PM