Inspections for the day of: Thursday, July 14, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00711 FIR-Aging Inspection7/14/20057/14/20057/15/2005 4:11:06 PM NR
Harvy is to find out job status
FIR03-00678 FIR-Aging Inspection7/14/20057/14/20057/15/2005 10:10:44 AM PASS
FIR04-00743 INSP-Sprinkler Rough-in/Hydro7/14/20057/14/20057/14/2005 4:19:22 PMPPASS
Sprinkler piping is ok to cover.
BLD04-00300 FIRE-Final Inspection7/14/20057/14/20057/14/2005 3:43:05 PMPPASS
Paint curbs per sheet C-2, final fire alarm permit, provide one hour fire rated room per plans.
BLD04-01513 FIRE-Final Inspection7/13/20057/14/20057/14/2005 12:06:04 PMAFAIL
doug; Phone #: ###-#### Provide exit discharge lighting and approved hardware at the first floor southeast exterior door or remove hardware and exit sign. Provide fire extinguishers as marked in red on drawing sheets A1 and A2. Provide/repair exit signs and emergency lights as marked on sheets E1 and E2. Provide missing door hardware on all doors.
FIR05-00156 INSP-Final Inspection7/14/20057/14/20057/14/2005 11:07:38 AMPCANC
Troy, We would like to schedule an inspection for late this afternoon if at all possible. Around 3:00 would work the best for us, but whatever you could work in would be acceptable. Please call me at ###-####, so that I can have everyone onsite as needed. Thankd Troy. Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
BLD05-01407 FIRE-Final Inspection7/13/20057/14/20057/14/2005 9:38:40 AMAPASS
Fire life safety finaled
FIR05-00317 INSP-Final Inspection7/13/20057/14/20057/14/2005 9:38:11 AMAPASS
Fire sprinkler pemit finaled
FIR05-00124 INSP-Conference7/14/20057/14/20057/14/2005 12:00:00 AMPDONE
I spoke to Dave with Debest about possible rated walls in the existing school. I referred him back to the architect. I also noted exposed wood including beams and 2x4's located above the ceiling that have no sprinkler protection.
FIR04-00718 INSP-Conference7/14/20057/14/20057/14/2005 12:00:00 AMPDONE
I met George with Romar to discuss the location of the a/v located in the middle of the ramp to the stage. The a/v in question is ok as installed 1" too low.
BLD05-01083 FIRE-Conference7/14/20057/14/20057/14/2005 12:00:00 AMPDONE
A duct smoke detector has been placed on the new hvac unit but has no wiring powering it or connecting it to the existing fire alarm system. Per contractor and plans the unit is under the 2000cfm limit and the duct smoke detector is not required.