Inspections for the day of: Friday, July 14, 2006.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01297 ELE-Aging Inspection7/14/20067/14/20067/17/2006 1:59:00 PM NR
suc
ELE06-02314 Final7/14/20067/14/20067/14/2006 4:52:56 PMPPASS
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE06-02596 Temporary Service7/14/20067/14/20067/14/2006 4:32:31 PMPFAIL
Scheduled by a contractor via Hello! on 7/14/2006 at 11:26:28 AM. Contact: ###-####. called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 230.24(B)(1) lowest point of drip loop for service shall be 10' above finished grade
ELE06-02604 Permanent Service7/14/20067/14/20067/14/2006 4:24:36 PMPPASS
kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
ELE06-01821 Final7/14/20067/14/20067/14/2006 3:32:03 PMPFAIL
tim; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley bld says vanilla, no tenant, elect ok to final, told contr to get numbers and permits in order and inspection card, then recall
ELE06-02605 Electrical Rough-In7/14/20067/14/20067/14/2006 2:31:19 PMPPART
butch - underground; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover ne part only
ELE06-02113 Final7/14/20067/14/20067/14/2006 2:02:47 PMPFAIL
chris ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called left corr notice,nec 300.11(A) boxes shall be securely fastened in place (ceiling cans), 210.62 showroom receptacle shall be provided, 110.22 each disconnect shall be legible and durable and marked and suitable for environment
ELE06-02364 Electrical Rough-In7/14/20067/14/20067/14/2006 1:32:05 PMPPART
Scheduled by a contractor via Hello! on 7/14/2006 at 11:22:42 AM. Contact: ###-####. ok to cover se part running ns and ew from temp office and center of lot about 30' by center light
ELE06-02155 Permanent Service7/14/20067/14/20067/14/2006 12:47:53 PMPPASS
changing service from 100 amp to 200 thanx joe; Phone #: ###-#### Internet Inspection Request from: joe wheeler p/s u/g rec ok
ELE06-02549 Permanent Service7/14/20067/14/20067/14/2006 12:03:08 PMANH
permanent service thanx bob; Phone #: ###-#### Internet Inspection Request from: joe wheeler called, said to call when home
ELE06-00319 Electrical Rough-In7/13/20067/14/20067/14/2006 10:41:29 AMAPART
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL walls only except fire riser and elect ok to cover
ELE06-02604 Permanent Service7/13/20067/14/20067/14/2006 10:09:26 AMANR
kevin - ###-#### Internet Inspection Request from: Barbara Buckley called contr, need addressing, will check out
ELE06-00256 Final7/13/20067/14/20067/14/2006 9:30:10 AMAPASS
jack; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley checked u/g, ok to final
ELE06-02060 Final7/13/20067/14/20067/14/2006 9:18:32 AMAPASS
lloyd - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-02247 Final7/13/20067/14/20067/14/2006 9:00:21 AMAPASS
final on 1 room addition, homeowner will be there between 8 & 12. any questions call Andy @ ###-#### Internet Inspection Request from: Andy Rose ok to final
ELE06-02545 Temporary Service7/13/20067/14/20067/14/2006 8:45:58 AMAPASS
###-#### lisa t/s u/g n ok
ELE06-02539 Temporary Service7/13/20067/14/20067/14/2006 8:45:36 AMAPASS
###-#### lisa t/s u/g n ok
ELE06-02538 Temporary Service7/13/20067/14/20067/14/2006 8:45:16 AMAPASS
lisa; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley t/s u/g n ok
ELE06-02540 Temporary Service7/13/20067/14/20067/14/2006 8:44:55 AMAPASS
lisa; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley t/s u/g n ok
ELE06-00711 Permanent Service7/13/20067/14/20067/14/2006 8:18:59 AMAPASS
Scheduled by a contractor via Hello! on 7/13/2006 at 11:55:45 AM. Contact: ###-####. p/s u/g n ok (sticker on north xfmr) noted on plan
ELE06-00711 Electrical Rough-In7/13/20067/14/20067/14/2006 8:17:32 AMAPASS
Scheduled by a contractor via Hello! on 7/13/2006 at 1:12:44 PM. Contact: ###-####. added 2 floor boxes anop ok to pour