Inspections for the day of: Friday, July 14, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00134 INSP-Conference7/14/20067/14/20067/14/2006 4:04:56 PMPDONE
I spoke to Terry with Crane alarm about phone line concerns stemming from information I received from another contractor.
FIR05-00536 INSP-Sprinkler Rough-in7/14/20067/14/20067/14/2006 4:03:55 PMPPASS
The piping above the hardlids as marked on the 2nd and 3rd floor plans is ok to cover.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro7/13/20067/14/20067/14/2006 3:21:19 PMPPASS
The two heads and associated piping located in the first floor elevator lobby are ok to cover.
FIR06-00303 INSP-Sprinkler Rough-in7/13/20067/14/20067/14/2006 3:15:11 PMAPART
Underground sprinkler supply line as shown on the plans is 6". As installed piping is 4". I have allowed the piping to be buried under the condition that Bill Alexander is contacted and the overhead plans are modified to show this change.
FIR06-00219 FIR-Aging Inspection7/14/20067/14/20067/14/2006 2:59:15 PM NR
work is in progress
FIR05-00620 INSP-Final Inspection7/14/20067/14/20067/14/2006 2:57:52 PMPCANC
Scheduled by a contractor via Hello! on 7/14/2006 at 7:48:57 AM. Contact: ###-####.
FIR05-00659 INSP-Final Inspection7/14/20067/14/20067/14/2006 2:57:28 PMPFAIL
Forward flush of both backflow preventors passed. Still need to get letter stating it is ok to hang 6" main from a single truss
FIR05-00644 INSP-Sprinkler Rough-in7/13/20067/14/20067/14/2006 1:04:12 PMAPASS
North half of the first floor piping is ok to cover
BLD05-02650 FIRE-Final Inspection7/13/20067/14/20067/14/2006 11:03:04 AMAPASS
Life safety finaled
MIS06-00158 FIR-Final7/13/20067/14/20067/14/2006 10:47:23 AMAPASS
Life safety passed. Temporary address numbers are being used until sign is installed.
BLD06-00277 FIRE-Final Inspection7/12/20067/14/20067/14/2006 10:26:43 AMAPASS
Life safety finaled. The two doors that access the exterior patio are still a issue. George Slane is researching the issue still. Per George I'm to let the structural inspector address the issue, with George's decision at the building final.
FIR06-00198 INSP-Final Inspection7/14/20067/14/20067/14/2006 10:24:36 AMPPASS
Fire sprinkler permit finaled
BLD06-01117 FIRE-Final Inspection7/14/20067/14/20067/14/2006 9:40:09 AMAPASS
Life safety finaled.
BLD05-00775 FIRE-Final Inspection7/13/20067/14/20067/14/2006 9:39:40 AMAFAIL
The only life safety items looked at were the exit signs, emergency lights and the exit discharge lights. An exit discharge light is required at the main entry/exit. The overhead sprinkler system needs finaled as well as the fire alarm.
FIR05-00883 INSP-Sprinkler Rough-in/Hydro7/13/20067/14/20067/14/2006 9:37:43 AMAFAIL
Arrived at job site to witness the underground hydro test but they were not ready.