ELE08-00153
| Final | 7/14/2008 | 7/14/2008 | 7/14/2008 4:55:22 PM | P | PASS |
|
|
Chris is the onsite contact his cell number is ###-####. Phone #: ###-#### Internet Inspection Request from: Shawna Gates ok to final, gave survey for sign at house panel, bond hot and cold water at heaters,install common trip breakers for furniture, signed occupancy card, could not enter esc data
|
ELE08-01900
| Electrical Rough-In | 7/14/2008 | 7/14/2008 | 7/14/2008 4:04:08 PM | P | PASS |
|
|
Dan Phone #: ###-#### corrections made, ok to pour concrete encased electrode and to cover u/g house to change house, no esc this project
|
ESC08-00268
| General Inspection | 7/14/2008 | 7/14/2008 | 7/14/2008 3:37:22 PM | P | PASS |
|
|
looked ok
|
ESC08-00522
| General Inspection | 7/14/2008 | 7/14/2008 | 7/14/2008 3:36:24 PM | P | PASS |
|
|
looked ok
|
ESC06-00711
| General Inspection | 7/14/2008 | 7/14/2008 | 7/14/2008 3:34:37 PM | P | PASS |
|
|
looked ok
|
ELE08-01837
| Electrical Rough-In | 7/14/2008 | 7/14/2008 | 7/14/2008 3:33:31 PM | P | PASS |
|
|
richard Phone #: ###-#### corrections made, ric ok
|
ELE08-00873
| Electrical Rough-In | 7/14/2008 | 7/14/2008 | 7/14/2008 2:41:47 PM | P | FAIL |
|
|
ted Phone #: ###-#### met owner, gave corrections, BCC all make-up shall be done, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, shall staple nm within 8" of box
|
ELE08-01864
| Permanent Service | 7/11/2008 | 7/14/2008 | 7/14/2008 1:55:07 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Adam Staigle p/s o/h rec ok, no esc this project
|
ELE08-00143
| Final | 7/14/2008 | 7/14/2008 | 7/14/2008 12:51:56 PM | P | PASS |
|
|
Mike Phone #: ###-#### called contractor, ok to final
|
ELE08-01900
| Electrical Rough-In | 7/11/2008 | 7/14/2008 | 7/14/2008 10:35:59 AM | A | PART |
|
|
dan Phone #: ###-#### ok to cover inside building, shall clean up concrete encased electrode and recall and provide ground bar for panel, and change abrasion protection for gec, no esc this project
|
ELE08-01761
| Electrical Rough-In | 7/11/2008 | 7/14/2008 | 7/14/2008 9:42:38 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/11/2008 at 5:28:51 PM. Contact: ###-####. corrections made, ric ok, no esc this project
|
ELE08-01922
| Conference | 7/11/2008 | 7/14/2008 | 7/14/2008 9:06:46 AM | A | DONE |
|
|
jean Phone #: ###-#### reviewed requirements for concrete encased electrode, service and ri requirements, when to call for inspections etc., no esc this project
|
ELE08-01507
| Electrical Rough-In | 7/14/2008 | 7/14/2008 | 7/14/2008 9:06:07 AM | A | PART |
|
|
Hello we are ready for a ceiling grid inspection. Call if any problems or questions thanks. Phone #: ###-#### Internet Inspection Request from: Don Lustig called contractor, told builder ok to cover ceiling except 4 rows in main area. Electrical contractor shall strap mc within 12" of fixtures, 2 rows-center and south row, can see with few tiles left out- will call for am re-inspection, no esc this project
|
ELE08-01896
| Final | 7/9/2008 | 7/14/2008 | 7/12/2008 6:28:55 PM | A | CANC |
|
|
Lock box code is 0345. Any questions or concerns please call MIKE AT ###-#### or Clay at ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan Inspection cancelled from web by: Clay Morgan
|