Inspections for the day of: Monday, July 14, 2008.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01194 FIRE-Final Inspection7/14/20087/14/20087/14/2008 5:08:41 PMPPASS
fire life safety passed
FIR08-00413 INSP-Sprinkler Rough-in/Hydro7/11/20087/14/20087/14/2008 5:07:47 PMPPASS
See the city approved plans for the rooms where the sprinkler piping can be covered.
FIR08-00047 INSP-Final Inspection7/14/20087/14/20087/14/2008 3:46:52 PMPCANC
Cancelled due to time constraints.
FIR08-00214 INSP-Sprinkler Rough-in/Hydro7/14/20087/14/20087/14/2008 3:45:17 PMPPASS
hydro of fdc passed
FIR05-00806 INSP-Final Inspection7/11/20087/14/20087/14/2008 3:11:09 PMPFAIL
One pendant is missing and one pendant needs to be relocated 8" back to its original location and the 45 degree brace relocated or removed. These two items are in Service Bay 2459 and have been marked on the clean room copies of the city approved plans.
FIR08-00318 INSP-Final Inspection7/14/20087/14/20087/14/2008 2:47:55 PMPCANC
The fire sprinklers where not quite ready when I was there to do the inspection. Will be rescheduled for tomorrow morning.
FIR07-00902 INSP-Alarm Testing7/11/20087/14/20087/14/2008 2:47:20 PMPCANC
The fire sprinklers where not quite ready when I was there to do the inspection. Will be rescheduled for tomorrow morning.
FIR08-00284 INSP-Final Inspection7/11/20087/14/20087/14/2008 2:44:03 PMPCANC
The fire sprinkler contractor was not ready when I was there so the inspection is going to be rescheduled for tomorrow morning.
FIR07-00606 INSP-Sprinkler Rough-in7/11/20087/14/20087/14/2008 2:41:50 PMACANC
Cancelled due to time constraints. I left a message on pat's voice mail.
BLD08-00802 FIRE-Final Inspection7/11/20087/14/20087/14/2008 2:39:34 PMAFAIL
Pick a door that is to be the main entrance/exit. This door will need the thumbturn lock removed and keyed provided. All of the other doors will need the thumbturn locks removed. The provided fire extinguisher is too small. Provide a 2a10bc with a current inspection tag from a local licenced fire extinguisher contractor.
BLD07-01006 FIRE-Final Inspection7/11/20087/14/20087/14/2008 12:47:10 PMADEFR
I spoke to curtis at ###-#### and he stated that they were working with dave hanna on getting multiple permits cleaned up and this one should be done in the next couple of days. I told him to please involve forrest france.
FIR07-01018 INSP-Sprinkler Rough-in7/11/20087/14/20087/14/2008 12:37:12 PMAPART
The earthquake bracing as noted in the previous inspection has not been corrected and the upright heads on the second floor that were spaced too close together have not been corrected either. Leroy and I agreed they could be verified at the final inspection.
FIR07-00902 INSP-Sprinkler Rough-in/Hydro7/11/20087/14/20087/14/2008 12:35:29 PMAPASS
OH Hydro Inspection for the first floor passed
FIR08-00461 INSP-Sprinkler Rough-in/Hydro7/11/20087/14/20087/14/2008 10:32:35 AMADEFR
Jeff and I agreed to have Forrest continue the inspections on this project due to agreements on sidewall head placement at the air conditioning units.
BLD08-01112 FIRE-Alarm Testing7/11/20087/14/20087/14/2008 9:43:25 AMAPASS
Life safety passed.
BLD07-02448 FIRE-Final Inspection7/11/20087/14/20087/14/2008 8:27:11 AMAFAIL
Repair the exit discharge lights on the west side of the building. All other items are ok. It appears each tenant space will have a Benjamin Lane address.