Inspections for the day of: Wednesday, July 14, 2010.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01569 Final7/14/20107/14/20107/14/2010 4:21:40 PMPCANC
please give me a call half an hour before inspection thanks shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman wrong type request, see ri
ELE10-01569 Electrical Rough-In7/14/20107/14/20107/14/2010 4:21:27 PMPPASS
please give me a call half an hour before inspection thanks shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman ri ok
ELE10-01560 Electrical Rough-In7/14/20107/14/20107/14/2010 2:32:58 PMPPASS
Matt Phone #: ###-#### ri ok
ELE10-01564 Electrical Rough-In7/13/20107/14/20107/14/2010 1:31:47 PMPFAIL
Job Contact-Kotton-###-####. Cover inspection for walls. Located on Second floor in the south-east corner of bulding
Thanks Phone #: ###-#### >> Inspection requested via web by Lynn Cable called, left correction notice, NEC 300.4(D) cables and raceways shall be 1 1/4" from edge of framing members, BCC there shall be no wiring in channels of framing members, Note; corrections shall be made within 5 working days or further action will be taken
ELE09-01409 Final7/14/20107/14/20107/14/2010 12:50:02 PMPPASS
This is for a final in the kitchen area of Lowell. Contact Jeff if there are any questions. Phone #: ###-#### >> Inspection requested via web by Spencer Mclean ok to final, signed occupancy card
ELE10-01354 Electrical Rough-In7/13/20107/14/20107/14/2010 11:40:38 AMAPASS
Nick is the contract his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates basement walls only ok, service can't be changed because of too many disconnects without main, also ampacity of bus would be exceeded, several other violations regarding foreign piping over electrical gear, and remote service panel not correctly wired, shall meet requirements of NEC article 230, part V.
ELE10-01456 Permanent Service7/13/20107/14/20107/14/2010 10:35:29 AMAPASS
Bill Phone #: ###-#### p/s u/g n ok
ELE10-01455 Permanent Service7/13/20107/14/20107/14/2010 10:34:50 AMAPASS
Bill Phone #: ###-#### p/s u/g n ok
ELE10-00405 Final7/13/20107/14/20107/14/2010 10:08:54 AMAPASS
Key under mat Phone #: ###-#### >> Inspection requested via web by Dan Rohl ok to final
ELE10-01240 Final7/13/20107/14/20107/14/2010 9:18:09 AMAPASS
Please call John 1/2 hr prior to inspection for access.###-#### Phone #: ###-#### >> Inspection requested via web by Terry Scott ok to final, corrections made
ELE10-01463 Electrical Rough-In7/13/20107/14/20107/14/2010 8:55:58 AMAFAIL
Greg this is to inspect the celing tile Phone #: ###-#### called, left correction notice, NEC 314.25 all boxes shall be closed with covers, 300.11 cables and raceways shall not be supported by ceiling grids,725.25 abandoned low voltage cables shall be removed, BCC tiles shall be removed to inspect each fixture and any boxes in ceiling, NOTE; corrections shall be made within 5 working days or further action will be taken
ELE10-01560 Electrical Rough-In7/13/20107/14/20107/14/2010 8:02:01 AMANH
Matt Maloy ###-#### called, nh, left card, told to recall
ELE10-00055 DOC - Permit Expired7/14/20107/14/20107/14/2010 6:18:01 AMAPASS
no activity
ELE10-01031 Final7/14/20107/14/20107/14/2010 6:15:09 AMAPASS
ok to final
ELE10-00262 ELE-Aging Inspection7/14/20107/14/20107/14/2010 6:13:42 AM DONE
no activity
ELE10-00235 ELE-Aging Inspection7/14/20107/14/20107/14/2010 6:13:03 AM DONE
no activity
ELE08-02589 ELE-Aging Inspection7/14/20107/14/20107/14/2010 6:11:45 AM DONE
see doc expire
ELE08-02589 DOC - Permit Expired7/14/20107/14/20107/14/2010 6:11:34 AMAPASS
no activity
ELE08-02516 ELE-Aging Inspection7/14/20107/14/20107/14/2010 6:10:14 AM DONE
see doc expire
ELE08-02516 DOC - Permit Expired7/14/20107/14/20107/14/2010 6:09:58 AMAPASS
no activity