FIR05-00109
| INSP-Conference | 7/2/2010 | 7/7/2010 | | A | |
|
|
Follow up conference with Mike; ###-####
|
BLD10-01416
| FIRE-Final Inspection | 7/13/2010 | 7/14/2010 | 7/14/2010 2:57:39 PM | P | FAIL |
|
|
Remove the dead bolt and provide single action hardware on the office door, provide tagged fire extinguisher as discussed and install the missing ceiling tiles.
|
FIR10-00220
| INSP-Sprinkler Rough-in | 7/14/2010 | 7/14/2010 | 7/14/2010 2:50:21 PM | P | PASS |
|
|
The lobby area sprinkler piping is ok to cover. See the city approved plans for specific area marked with todays date.
|
FIR10-00032
| INSP-Sprinkler Rough-in | 7/14/2010 | 7/14/2010 | 7/14/2010 2:48:47 PM | P | PASS |
|
|
The sprinkler piping in phase 3B is ok to cover. See the city approved plans marked with todays date for specific area.
|
FIR03-00082
| INSP-Final Inspection | 7/14/2010 | 7/14/2010 | 7/14/2010 2:47:50 PM | P | PASS |
|
|
Permit finaled. The pendant spacing in the coolers has been corrected.
|
FIR09-00611
| INSP-Final Inspection | 7/13/2010 | 7/14/2010 | 7/14/2010 11:05:15 AM | A | FAIL |
|
|
Todays inspection was for the revised risers. The new inspectors tests and flow switches functioned correctly. Also inspected were the phase 13 sprinkler piping which can be covered. Sprinkler coverage is lacking in an entry foyer in this same area.
|
BLD10-01379
| FIRE-Final Inspection | 7/13/2010 | 7/14/2010 | 7/14/2010 10:39:04 AM | A | FAIL |
|
|
A wall has been removed which left several sprinkler pendants located too close to one another which will require a sprinkler permit, provide single action lever hardware on the three doors as discussed, provide tagged fire extinguisher, provide suite number and sticker at the main exit.
|