Inspections for the day of: Thursday, July 14, 2011.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00583 INSP-Sprinkler Rough-in7/14/20117/14/20117/14/2011 4:32:46 PMPPART
Previous correction items at the second floor and attic levels finished, okay to cover.
FIR10-00583 INSP-Supply line flush7/14/20117/14/20117/14/2011 4:29:12 PMPPART
UG fire supply line flush completed.
BLD11-00551 FIRE-Final Inspection7/14/20117/14/20117/14/2011 3:04:58 PMPFAIL
Correction items include; remove manual thumbturn at the main entry/exit and provide approved hardware and signage, provide test method for the new duct detector including appropriate remote indicator/key switch.
BLD11-01550 FIRE-Final Inspection7/14/20117/14/20117/14/2011 3:00:57 PMPPASS
Fire life safety inspection completed satisfactory.
BLD11-01196 FIRE-Final Inspection7/14/20117/14/20117/14/2011 1:44:50 PMPPASS
Reinspection passed, corrections finished. Life safety finaled.
BLD11-00760 FIRE-Final Inspection7/14/20117/14/20117/14/2011 12:54:56 PMPFAIL
Need project related fire sprinkler permit final request, adjust exit sign directionals as discussed, door hardware at the server room should be reversed.
BLD11-00894 FIRE-Final Inspection7/13/20117/14/20117/14/2011 12:49:49 PMPPASS
Fire life safety passed.
FIR11-00293 INSP-Final Inspection7/14/20117/14/20117/14/2011 12:38:37 PMAPASS
Fire sprinkler permit finaled.
FIR11-00248 INSP-Final Inspection7/13/20117/14/20117/14/2011 12:33:44 PMAPASS
Fire alarm permit work passed functional testing. Permit final approved.
FIR11-00320 INSP-Final Inspection7/13/20117/14/20117/14/2011 11:27:34 AMAPASS
Fire alarm testing passed. Permit finaled.
BLD11-01055 FIRE-Final Inspection7/13/20117/14/20117/14/2011 10:47:10 AMAPASS
Life safety completed acceptable. Contractor to post fire extinguisher adjacent to the main entry/exit door as discussed.
BLD11-01196 FIRE-Final Inspection7/13/20117/14/20117/14/2011 10:45:29 AMAFAIL
Correction items include; repair one exit sign and one emergency light at the main entry area, provide directional arrows per plan at two exit signs in the east and west central core area, certification tag at the PFE near the second exit is 6 yrs. overdue. Noted wall infill at the mechanical room per plan review annotation is not completed.