Inspections for the day of: Thursday, July 14, 2011.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00272 INSP-Final Inspection7/13/20117/14/20117/14/2011 3:24:51 PMPFAIL
Street, city and state address has not been set up and one smoke detector is located too close to an air grill.
FIR11-00080 INSP-Final Inspection7/14/20117/14/20117/14/2011 3:21:08 PMPFAIL
Ok to final when the project related fire alarm permit is finaled.
BLD10-02263 FIRE-Final Inspection7/14/20117/14/20117/14/2011 3:14:54 PMPPASS
life safety passed
BLD11-01322 FIRE-Final Inspection7/13/20117/14/20117/14/2011 3:12:27 PMAPASS
Life safety passed.
FIR11-00167 INSP-Sprinkler Rough-in/Hydro7/13/20117/14/20117/14/2011 11:34:01 AMAFAIL
The hydro test could not be performed due to additional upright heads required around the x-ray room and on the back side of the roof access door. Also the most current set of plans was not on site.
BLD11-01186 FIRE-Final Inspection7/13/20117/14/20117/14/2011 9:58:35 AMAPASS
Life safety passed. Taylor Brothers will have the two small fire extinguishers replaced this afternoon per Mary.
FIR11-00159 INSP-Sprinkler Rough-in7/13/20117/14/20117/14/2011 9:20:12 AMAPART
Todays inspection was to verify that several of the previous corrections had been addressed on the lower level. They have been marked "ok" in red ink. One pendant still had not been installed in a hard lid and the earthquake bracing for the mains was incorrect.