BLD15-01638
| FIRE-Final Inspection | 7/13/2015 | 7/14/2015 | 7/14/2015 3:08:43 PM | A | CANC |
|
|
Thanks Matt, Phone #: ###-#### Inspection requested via web by Richard Schultz
|
BLD15-00487
| FIRE-Final Inspection | 7/14/2015 | 7/14/2015 | 7/14/2015 2:47:26 PM | P | FAIL |
|
|
Life safety will be ok to final when the project related fire alarm and fire sprinkler permits are finaled
|
FIR15-00481
| INSP-Final Inspection | 7/14/2015 | 7/14/2015 | 7/14/2015 2:45:31 PM | P | FAIL |
|
|
Second flow switch is not activating the outside alarm bell
|
FIR15-00298
| INSP-Final Inspection | 7/14/2015 | 7/14/2015 | 7/14/2015 2:32:15 PM | P | FAIL |
|
|
Painted head and the outside alarm bell did not function on the second flow switch
|
FIR15-00488
| INSP-Final Inspection | 7/13/2015 | 7/14/2015 | 7/14/2015 2:30:41 PM | A | PASS |
|
|
Permit finaled
|
FIR15-00317
| INSP-Final Inspection | 7/14/2015 | 7/14/2015 | 7/14/2015 2:19:43 PM | P | PASS |
|
|
permit finaled
|
FIR15-00449
| INSP-Final Inspection | 7/14/2015 | 7/14/2015 | 7/14/2015 2:18:31 PM | P | PASS |
|
|
permit finaled
|
BLD15-00486
| FIRE-Final Inspection | 7/14/2015 | 7/14/2015 | 7/14/2015 2:18:01 PM | P | PASS |
|
|
life safety passed
|
FIR15-00334
| INSP-Alarm Testing | 7/13/2015 | 7/14/2015 | 7/14/2015 12:03:43 PM | P | PART |
|
|
24 hr air test Boise Spectrum - Bldg B started at 9:00am with pressure marked on guage
|
FIR15-00331
| INSP-Alarm Testing | 7/13/2015 | 7/14/2015 | 7/14/2015 12:02:33 PM | P | PASS |
|
|
24 hr air test Boise Spectrum - Bldg C passed
|
FIR15-00411
| INSP-Final Inspection | 7/13/2015 | 7/14/2015 | 7/14/2015 10:25:58 AM | A | PASS |
|
|
Permit finaled
|
FIR15-00415
| INSP-Sprinkler Rough-in/Hydro | 7/13/2015 | 7/14/2015 | 7/14/2015 9:16:16 AM | A | FAIL |
|
|
The overhead hydro failed due to visible loss on the guage. I also noted that in the northwest corner a wall is going to block coverage of an upright head into the small room just off the corridor.
|
FIR15-00323
| INSP-Sprinkler Rough-in/Hydro | 7/13/2015 | 7/14/2015 | 7/14/2015 8:37:25 AM | A | PASS |
|
|
Overhead rough-in and tenting passed. Piping can be covered.
|
FIR15-00361
| INSP-Sprinkler Rough-in/Hydro | 7/13/2015 | 7/14/2015 | 7/14/2015 8:36:40 AM | A | PASS |
|
|
Overhead hydro test passed
|