Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF15-00015 INSP-Sprinkler Rough-in7/13/20157/14/20157/14/2015 3:13:02 PMANR
Not ready per phone call with Richard.
FIR15-00332 INSP-Sprinkler Rough-in7/13/20157/14/20157/14/2015 2:09:49 PMPPASS
Rough-in inspection pass. Ok to cover.
NAF14-00023 INSP-Sprinkler Rough-in/Hydro7/13/20157/14/20157/14/2015 1:17:31 PMAPART
When looking at the townhomes, the one to the right passed the hydro. The system for the left townhouse failed: dropped 5 psi over 2 hrs. Leak could not be readily found.

Supply line in still to be corrected to 1 1/4".