NAF15-00015
| INSP-Sprinkler Rough-in | 7/13/2015 | 7/14/2015 | 7/14/2015 3:13:02 PM | A | NR |
|
|
Not ready per phone call with Richard.
|
FIR15-00332
| INSP-Sprinkler Rough-in | 7/13/2015 | 7/14/2015 | 7/14/2015 2:09:49 PM | P | PASS |
|
|
Rough-in inspection pass. Ok to cover.
|
NAF14-00023
| INSP-Sprinkler Rough-in/Hydro | 7/13/2015 | 7/14/2015 | 7/14/2015 1:17:31 PM | A | PART |
|
|
When looking at the townhomes, the one to the right passed the hydro. The system for the left townhouse failed: dropped 5 psi over 2 hrs. Leak could not be readily found.
Supply line in still to be corrected to 1 1/4".
|