Inspections for the day of: Thursday, July 14, 2016.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorKatie Marron
TitleFIRE INSPECTOR
Phone #395-7809
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF16-00018 INSP-Final7/13/20167/14/20167/14/2016 1:40:07 PMPPASS
Life safety pass.
GCB15-00090 FIRE-Conference7/12/20167/14/20167/14/2016 10:58:30 AMADONE
Onsite conference to discuss oxygen generator & vacuum equipment room, oxygen storage room and nitrogen storage room requirements. The proposed oxygen generator has a storage capacity of 60 gallons which is below the threshold in IFC 105.6.8, the client is limited to the 60 gallon size generator and not larger models. Separate compressed backup oxygen. tanks will be stored in a rated, vented closet. The nitrogen tanks are in a separate room and below the threshold of IFC 105.6.8. A louver is provide in the room with the oxygen generator and its operation coincides with the generators (field verify). Continuous ventilation is provided for these spaces.