ELE17-02171
| Final | 7/11/2017 | 7/14/2017 | 7/14/2017 3:06:43 PM | P | PASS |
|
|
Please contact Mike at ###-#### for property access. They are there until 4pm Phone #: ###-#### Inspection requested via web by jamie berg Final ok
|
ELE17-02171
| Electrical Rough-In | 7/14/2017 | 7/14/2017 | 7/14/2017 2:48:08 PM | P | PASS |
|
|
Please contact Mike at ###-#### for property access. They are there until 4pm Phone #: ###-#### Inspection requested via web by jamie berg Rough in to new 60 amp circuit for AC unit at rear of building ok
|
ELE17-00800
| Final | 7/14/2017 | 7/14/2017 | 7/14/2017 2:29:44 PM | P | CANC |
|
|
Requesting an inspection after 3:30 pm. Call or text when in route as residence is occupied and I am not on site. Thank you. Phone #: ###-#### Inspection requested via web by Cortney Hopper Called contact and left message unable to inspect due to time needed, not in area in late afternoon.
|
ELE17-02168
| Rough-In Permanent Service | 7/10/2017 | 7/14/2017 | 7/14/2017 2:24:23 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson WUI zone soffit can fire barriers not done. Remote hood control wire junction point has exposed conductors that shall be installed in a box or conduit as per 300.3. Access will be provided in fir down to enforce at final. Interior Rough in ok cover p/s u/g n ok
|
ELE17-02246
| Rough-In Permanent Service | 7/13/2017 | 7/14/2017 | 7/14/2017 1:20:30 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Paula Gratiot Wui Zone soffit can barriers not in place. Interior only rough in ok cover p/s u/g n ok
|
ELE17-01357
| Final | 7/14/2017 | 7/14/2017 | 7/14/2017 11:17:07 AM | A | PASS |
|
|
Final inspection for shed. I believe permit ELE17-01809 is ready for inspection as well. Contractor was waiting for me to build a wall between equipment area and bathroom. Phone #: ###-#### Inspection requested via web by Dean Perman Final ok
|
ELE17-01809
| Final | 7/14/2017 | 7/14/2017 | 7/14/2017 10:41:33 AM | P | PASS |
|
|
Disconnecting means in place. Final ok
|
ELE17-02115
| Final | 7/13/2017 | 7/14/2017 | 7/14/2017 10:40:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tyler Bowen Final ok
|
ELE14-02618
| Final | 7/13/2017 | 7/14/2017 | 7/14/2017 10:03:39 AM | A | FAIL |
|
|
There should be someone there. There is a lock box just in case 4320. Steve would be your contact ###-####. If you have any questions please call Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan 240.4- Max overcurrent device for 14 gauge wire 15 amps. 20 amp installed on garage circuit. 250.53- Grounding electrode conductor and interbond bar shall be secured to structure. 422.30- A disconnecting means shall be provided for water heater. 110.25 Lockout acceptable.
|
ELE17-01337
| Electrical Rough-In | 7/13/2017 | 7/14/2017 | 7/14/2017 9:28:33 AM | A | PASS |
|
|
We are requesting an underground inspection for tomorrow morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Contractor providing 2nd concrete encased for pool equipment. Equipment grounding conductor shall be minimum of #4 to this room to be added to grounding electrode system. Rough in ok cover
|
ELE17-02198
| Permanent Service | 7/13/2017 | 7/14/2017 | 7/14/2017 8:39:42 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Louis Keller 200 amp service on pole located eastside of back yard. p/s o/h n ok
|
ELE15-03035
| Final | 7/13/2017 | 7/14/2017 | 7/14/2017 7:27:04 AM | P | CANC |
|
|
Contact Paul at ###-####. Thank You Phone #: ###-#### >> Inspection requested via web by Steve Blackmer Inspection cancelled from web by: Steve Blackmer
|