FIR17-00022
| INSP-Final Inspection | 7/13/2017 | 7/14/2017 | 7/14/2017 11:27:46 AM | P | FAIL |
|
|
Provide testing of the outside alarm bell when installed, provide an updated map as discussed and provide as-builts to myself and plan review with the changes to the notification circuts. Need to test the notification devices and the manual pull station. All other devices have been tested and signals verified.
|
FIR16-00806
| INSP-Final Inspection | 7/13/2017 | 7/14/2017 | 7/14/2017 11:24:03 AM | P | FAIL |
|
|
Provide test papers and testing of the outside alarm bell when installed. Forward flush passed
|
FIR17-00080
| INSP-Final Inspection | 7/13/2017 | 7/14/2017 | 7/14/2017 9:20:22 AM | A | FAIL |
|
|
The fire alarm system was not ready to verify the tamper/flow/pressure switches, need system zone map, signage on door, and plan modifications showing the dry pipe valves used. Also missing the spare sprinkler cabinet. The forward flush test passed.
|
BLD16-03864
| FIRE-Final Inspection | 7/13/2017 | 7/14/2017 | 7/14/2017 8:30:08 AM | A | FAIL |
|
|
Provide sticker at the exit, provide fire extinguisher as discussed and provide address as discussed
|
FIR16-00738
| INSP-Conference | 7/13/2017 | 7/14/2017 | 7/14/2017 7:45:26 AM | A | DONE |
|
|
Kitchen area piping is ok to cover.
|
FIR17-00118
| INSP-Final Inspection | 7/12/2017 | 7/14/2017 | 7/14/2017 6:06:46 AM | A | CANC |
|
|