Inspections for the day of: Tuesday, July 14, 2020.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-04163 Rough-in7/14/20207/14/20207/14/2020 2:04:07 PMPPASS
1st Floor back of house, 1st floor 6th street lobby. Please call Rob prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator - Okay to cover hard lid on 6th st. side of lobby, okay to cover grid ceilings in back of house and kitchen
MEC19-05425 Rough-in7/13/20207/14/20207/14/2020 10:24:29 AMAPART
It be for the shaft duct to be covered on floors 3-9 Phone #: ###-#### Inspection requested via web by Amanda Farnsworth - Okay to build shaft wall on floors 3, 5, 6, 7, 8 & 9. Need to repair or replace fire blanket on outside of the damper sleeve on 4th floor. If repaired need to provide the manufactures instruction for repairing when reinspected.