ELE02-01915
| Final | 7/15/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 07/15/2002 at 07:08:47. Contact: ###-####. cor. posted called 300.10 shall bond conduits at non metallic boxes not at metallic boxes 7/15/2002 11:13:48 AM
|
ELE02-01973
| Final | 7/12/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | A | PASS |
|
|
###-#### jean ok 7/15/2002 10:21:46 AM
|
ELE02-01946
| Electrical Rough-In | 7/12/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | A | FAIL |
|
|
###-#### cor. posted called 300.4 (A)(1)&(D) 210.52 (A) needs 2 outlets for wall space dinning rm 11.14(B) grd splices loose, 314.16 box fill no violation to be retained 2 box in kit. 7/15/2002 1:08:55 PM
|
ELE02-01598
| Electrical Rough-In | 7/12/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | P | PART |
|
|
###-#### Gary (home) electrode ok for concrete cover and conference ok 7/15/2002 4:14:08 PM
|
ELE02-02127
| Rough-In Permanent Service | 7/15/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 07/15/2002 at 07:40:13. Contact: ###-####.not all cor. made 300.4(A)(1)and (D), and 314.20 boxes not set flush with finish surface, too many cables under staples , 250.148 j box in basement, and needs new 4 wire feed to range? called left phone number 7/15/2002 6:42:01 PM
|
ELE00-04435
| Electrical Rough-In | 7/15/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | P | PART |
|
|
###-#### bob ok to cover electrode with dirt 7/15/2002 3:12:42 PM
|
ELE02-02147
| Permanent Service | 7/15/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | P | PASS |
|
|
cell ###-####- clyde smart p/s oh rec. fire job ok called Id power 7/15/2002 11:47:14 AM
|
ELE02-02088
| Rough-In Permanent Service | 7/15/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 07/15/2002 at 09:01:30. Contact: ###-####. r/i ok
p/s o/h new ok 7/15/2002 4:39:36 PM
|
ELE02-01136
| Electrical Rough-In | 7/15/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | P | PASS |
|
|
###-#### SERVICE INSPECT JOHN
p/s u/g new ok 7/15/2002 5:34:37 PM
|
ELE02-01138
| Final | 7/15/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | P | PASS |
|
|
fn susie ###-#### re-insp for sign corrections made ok 7/15/2002 2:36:14 PM
|
ELE01-02385
| Electrical Rough-In | 7/15/2002 | 7/15/2002 | 7/15/2002 12:00:00 AM | P | PART |
|
|
PERMIT TO EXPIRE PLEASE CALL ###-#### BURT conference ok 7/15/2002 6:03:09 PM
|