Inspections for the day of: Thursday, July 15, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00891 FIRE-Final Inspection7/12/20047/15/20047/15/2004 12:00:00 AMAPASS
Fire life safety finaled 7/15/2004 8:45:35 AM
FIR04-00341 INSP-Final Inspection7/13/20047/15/20047/15/2004 12:00:00 AMACANC
Per contractor to be rescheduled for tomorrow 7/15/2004 8:58:26 AM
FIR04-00353 INSP-Final Inspection7/13/20047/15/20047/15/2004 12:00:00 AMAPASS
Permit finaled 7/15/2004 8:59:23 AM
FIR03-00779 INSP-Sprinkler Rough-in/Hydro7/14/20047/15/20047/15/2004 12:00:00 AMAPART
Hydro tests for both dry systems are ok. 24 hour test on the second dry system started at 12:45 at 67psi 7/15/2004 12:44:05 PM
BLD04-01019 FIRE-Alarm Testing7/15/20047/15/20047/15/2004 12:00:00 AMPPASS
fire alarm portion of the correction list has been corrected 7/15/2004 3:59:33 PM
FIR04-00300 INSP-Sprinkler Rough-in7/15/20047/15/20047/15/2004 12:00:00 AMPPASS
Sprinkler piping above the hard lid areas are ok for cover. I also looked at the main and branchline sizing, hangers and earthquake bracing. They are ok as well. Sprig ups, drops and return bends have not been inspected since not all work is complete. 7/15/2004 2:33:21 PM
FIR04-00404 INSP-Sprinkler Rough-in7/15/20047/15/20047/15/2004 12:00:00 AMPFAIL
Provide hanger on the horizontal piping that is currently laying on a piece of unattached uni-strut 7/15/2004 2:34:56 PM
FIR04-00404 INSP-Final Inspection7/15/20047/15/20047/15/2004 12:00:00 AMPFAIL
Rough-in failed 7/15/2004 2:35:53 PM