Inspections for the day of: Friday, July 15, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00510 FIR-Aging Inspection7/8/20057/15/20057/18/2005 3:07:12 PMAFAIL
I left another message on Mikes phone requesting job status.
FIR04-00684 INSP-Sprinkler Rough-in/Hydro7/15/20057/15/20057/15/2005 4:20:07 PMPPASS
Canopy is ok to cover. Eq bracing and upright have been added
FIR05-00170 INSP-Final Inspection7/12/20057/15/20057/15/2005 3:53:18 PMPFAIL
Contractor tripped the wrong dry system. Per Bill Alexander if the new dry pipe valve exceeds 60 seconds for water at the inspectors test the total capacity of this dry pipe system will need to be provided to the inspector. Will also need to verify signals to panel and monitoring agency.
BLD04-00300 FIRE-Final Inspection7/15/20057/15/20057/15/2005 3:46:07 PMPCANC
Request for temp; ###-####
FIR05-00069 INSP-Final Inspection7/15/20057/15/20057/15/2005 3:42:51 PMPPASS
Permit finaled
FIR05-00156 INSP-Final Inspection7/15/20057/15/20057/15/2005 3:41:59 PMPCANC
Request for temp
BLD04-01513 FIRE-Final Inspection7/15/20057/15/20057/15/2005 3:41:24 PMPCANC
Request for temp; ###-####
BLD05-01476 FIRE-Final Inspection7/15/20057/15/20057/15/2005 2:40:41 PMPPART
A temporary occupancy was given until three emergency lights have been added as discussed. One goes into the breakroom and two in the east open office
FIR05-00388 INSP-Final Inspection7/15/20057/15/20057/15/2005 2:39:23 PMPPASS
Fire sprinklers finaled
BLD05-00353 FIRE-Final Inspection7/12/20057/15/20057/15/2005 1:59:56 PMPFAIL
april; Phone #: ###-#### Still need to remove the manual flush bolts from the main exit. All other items corrected.
FIR05-00156 INSP-Final Inspection7/14/20057/15/20057/15/2005 10:43:15 AMPCANC
Troy, Here we go again. Please let us know what time will work for you tomorrow. Thanks. Jason (###-####); Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
BLD05-01476 FIRE-Final Inspection7/15/20057/15/20057/15/2005 9:29:57 AMAFAIL
Final fire sprinkler permit, repair exit signs and emergency lights. Additional devices may be required. I need to verify wether door mags will be an issue.
FIR05-00388 INSP-Final Inspection7/13/20057/15/20057/15/2005 8:58:19 AMAFAIL
Need remaining ceiling tile installed at sprinkler pendants before finaling
FIR03-00678 INSP-Final Inspection7/15/20057/15/20057/15/2005 12:00:00 AMPPASS
permit finaled
MIS04-00298 FIR-Final7/14/20057/15/20057/14/2005 3:46:11 PMAPART
###-#### A temporary occupancy was given until items listed have been corrected. Provide annual inspection for the existing fire extinguisher, provide fire extinguisher in basement, provide approved door hardware on the west exterior door. Lever or crashbar is ok. Provide approved door hardware on south exterior doors. Remove deadbolts (2x4 & keyed deadbolts). Lever hardware is ok.