FIR03-00510
| FIR-Aging Inspection | 7/8/2005 | 7/15/2005 | 7/18/2005 3:07:12 PM | A | FAIL |
|
|
I left another message on Mikes phone requesting job status.
|
FIR04-00684
| INSP-Sprinkler Rough-in/Hydro | 7/15/2005 | 7/15/2005 | 7/15/2005 4:20:07 PM | P | PASS |
|
|
Canopy is ok to cover. Eq bracing and upright have been added
|
FIR05-00170
| INSP-Final Inspection | 7/12/2005 | 7/15/2005 | 7/15/2005 3:53:18 PM | P | FAIL |
|
|
Contractor tripped the wrong dry system. Per Bill Alexander if the new dry pipe valve exceeds 60 seconds for water at the inspectors test the total capacity of this dry pipe system will need to be provided to the inspector. Will also need to verify signals to panel and monitoring agency.
|
BLD04-00300
| FIRE-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 3:46:07 PM | P | CANC |
|
|
Request for temp; ###-####
|
FIR05-00069
| INSP-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 3:42:51 PM | P | PASS |
|
|
Permit finaled
|
FIR05-00156
| INSP-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 3:41:59 PM | P | CANC |
|
|
Request for temp
|
BLD04-01513
| FIRE-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 3:41:24 PM | P | CANC |
|
|
Request for temp; ###-####
|
BLD05-01476
| FIRE-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 2:40:41 PM | P | PART |
|
|
A temporary occupancy was given until three emergency lights have been added as discussed. One goes into the breakroom and two in the east open office
|
FIR05-00388
| INSP-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 2:39:23 PM | P | PASS |
|
|
Fire sprinklers finaled
|
BLD05-00353
| FIRE-Final Inspection | 7/12/2005 | 7/15/2005 | 7/15/2005 1:59:56 PM | P | FAIL |
|
|
april; Phone #: ###-#### Still need to remove the manual flush bolts from the main exit. All other items corrected.
|
FIR05-00156
| INSP-Final Inspection | 7/14/2005 | 7/15/2005 | 7/15/2005 10:43:15 AM | P | CANC |
|
|
Troy, Here we go again. Please let us know what time will work for you tomorrow. Thanks. Jason (###-####); Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
BLD05-01476
| FIRE-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 9:29:57 AM | A | FAIL |
|
|
Final fire sprinkler permit, repair exit signs and emergency lights. Additional devices may be required. I need to verify wether door mags will be an issue.
|
FIR05-00388
| INSP-Final Inspection | 7/13/2005 | 7/15/2005 | 7/15/2005 8:58:19 AM | A | FAIL |
|
|
Need remaining ceiling tile installed at sprinkler pendants before finaling
|
FIR03-00678
| INSP-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 12:00:00 AM | P | PASS |
|
|
permit finaled
|
MIS04-00298
| FIR-Final | 7/14/2005 | 7/15/2005 | 7/14/2005 3:46:11 PM | A | PART |
|
|
###-#### A temporary occupancy was given until items listed have been corrected. Provide annual inspection for the existing fire extinguisher, provide fire extinguisher in basement, provide approved door hardware on the west exterior door. Lever or crashbar is ok. Provide approved door hardware on south exterior doors. Remove deadbolts (2x4 & keyed deadbolts). Lever hardware is ok.
|