Inspections for the day of: Tuesday, July 15, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-01288 Final7/14/20087/15/20087/15/2008 4:06:42 PMPPASS
Rick Phone #: ###-#### met owner, ok to final this permit, others still may go on, no esc this project
ELE08-00929 ELE-Aging Inspection7/15/20087/15/20087/15/2008 3:35:54 PM DONE
see final
ELE08-00929 Final7/15/20087/15/20087/15/2008 3:35:07 PMPPASS
looked at signs, ok to final, no esc this project
ELE08-00926 ELE-Aging Inspection7/15/20087/15/20087/15/2008 3:29:02 PM DONE
see final
ELE08-00926 Final7/15/20087/15/20087/15/2008 3:28:43 PMPPASS
looked at signs, ok to final, no esc this project
ESC06-01387 General Inspection7/15/20087/15/20087/15/2008 3:06:52 PMPPASS
looked ok
ELE08-01083 Electrical Rough-In7/15/20087/15/20087/15/2008 3:04:24 PMPFAIL
Morgan Please call 30 min before going out Phone #: ###-#### met owner, gave corrections, NEC 300.14 at least 6" free length conductor shall be left at each box where it emerges to splice or terminate, 312.5 shall provide abrasion protection for all conductors entering box,250.80 metal enclosures shall be grounded
ESC07-01052 General Inspection7/15/20087/15/20087/15/2008 1:54:00 PMPPASS
looked ok
ELE07-03457 Electrical Rough-In7/15/20087/15/20087/15/2008 1:28:55 PMPFAIL
Joe Phone #: ###-#### met contractor, uf cable shall be min 24" deep per NEC 300.5, will call back later
ELE07-04131 Permanent Service7/15/20087/15/20087/15/2008 12:57:47 PMPFAIL
service inspection Phone #: ###-#### Internet Inspection Request from: Spencer Mclean literature says suitable for service entrance, but no manufacturer label on gear, told electrician that factory has to put on, nobody else can affix label,
ELE08-01832 Permanent Service7/14/20087/15/20087/15/2008 11:05:33 AMAPASS
We are complete with this Qwest Ped and ready for Permanent Service. Thank you. Phone #: ###-#### Internet Inspection Request from: BRENDA HURST p/s u/g n ok, no esc this project
ELE08-01939 Electrical Rough-In7/14/20087/15/20087/15/2008 10:15:26 AMAPASS
###-#### Internet Inspection Request from: Todd Holbrook ric ok, no esc this project
ELE08-01939 Final7/15/20087/15/20087/15/2008 10:04:27 AMAPASS
###-#### Internet Inspection Request from: Todd Holbrook ok to final, signed occupancy card, no esc this project
ELE08-01865 Final7/14/20087/15/20087/15/2008 9:24:57 AMAPASS
Jim Phone #: ###-#### called contractor to label rest of panel, ok to final, no esc this project
ELE08-01833 Permanent Service7/14/20087/15/20087/15/2008 8:57:42 AMAPASS
We are complete with this Qwest Ped and ready for Permanent Service. Thank you. Phone #: ###-#### Internet Inspection Request from: BRENDA HURST p/s u/g n ok, no esc this project
ELE08-01834 Permanent Service7/14/20087/15/20087/15/2008 8:27:34 AMAPASS
We are complete with this Qwest Ped and ready for Permanent Service. Thank you. Phone #: ###-#### Internet Inspection Request from: BRENDA HURST p/s u/g n ok, no esc this project
ELE08-01507 Electrical Rough-In7/14/20087/15/20087/15/2008 8:05:36 AMAPASS
Hello i secured the flex whip on the center fixtures ready for reinspect.Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig corrections made, ok to finish ceiling cover, no esc this project