Inspections for the day of: Wednesday, July 15, 2009.
Number of inspections: 37
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00033 INSP-Sprinkler Rough-in7/8/20097/15/20097/16/2009 8:09:56 AMPPART
Fire pump curve certification passed pending acceptance of the non-functioning PLD due to possible water surge. Lucas with Peerless Pump stated that this is not a problem during a fire condition. The pump provided 472 gpm at 150% which is more than required.
FIR09-00033 INSP-Sprinkler Rough-in7/8/20097/15/20097/16/2009 8:07:32 AMAFAIL
Time tests for double interlock preaction systems at freezers unable to be completed due valves could not be set up.
FIR09-00345 INSP-Final Inspection7/15/20097/15/20097/15/2009 4:30:41 PMPCANC
Cancelled due to time constraints. Rescheduled for tomorrow with life safety inspection.
FIR09-00395 INSP-Sprinkler Rough-in7/15/20097/15/20097/15/2009 4:28:16 PMPCANC
Cancelled due to time constraints. Rescheduled for tomorrow.
FIR09-00397 INSP-Final Inspection7/14/20097/15/20097/15/2009 4:25:24 PMAPASS
permit finaled
FIR09-00087 INSP-Alarm Testing7/14/20097/15/20097/15/2009 2:02:39 PMPPASS
Permit finaled.
BLD04-01154 FIRE-Final Inspection7/14/20097/15/20097/15/2009 2:02:05 PMAFAIL
Provide emergency lights in the basement storage rooms and in the stairwell next to the elevator as per the approved plans. Provide exit signs in the basement storage rooms as per the life safety drawings or provide verification from the plan reviewer they can be deleted. The open DeBest Fire Protection FIR permits are to be disregarded.
FIR09-00255 INSP-Sprinkler Rough-in/Hydro7/15/20097/15/20097/15/2009 12:53:31 PMACANC
duplicate inspection
BLD09-00453 FIRE-Final Inspection7/15/20097/15/20097/15/2009 12:52:11 PMPPASS
life safety passed
FIR09-00258 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:50:42 PMPPASS
permit finaled
FIR09-00256 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:49:44 PMPPASS
permit finaled
FIR09-00300 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:48:39 PMAPASS
permit finaled
FIR09-00298 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:47:00 PMAPASS
permit finaled
FIR09-00057 FIR-Aging Inspection7/15/20097/15/20097/15/2009 12:24:56 PM NR
wip
FIR08-00724 INSP-Final Inspection7/15/20097/15/20097/15/2009 12:20:18 PMPCANC
Please call 30 min prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton Inspection cancelled from web by: Jeff Walton
BLD09-00457 FIRE-Final Inspection7/15/20097/15/20097/15/2009 12:14:06 PMPPASS
life safety passed
BLD09-00455 FIRE-Final Inspection7/15/20097/15/20097/15/2009 12:13:38 PMPPASS
life safety passed
FIR09-00250 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:12:29 PMPPASS
Permit finaled
FIR09-00249 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:11:59 PMPPASS
Permit finaled
FIR09-00248 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:11:31 PMPPASS
Permit finaled
FIR09-00303 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:09:39 PMAPASS
Permit finaled
FIR09-00302 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:09:04 PMAPASS
Permit finaled
FIR09-00301 INSP-Final Inspection7/14/20097/15/20097/15/2009 12:08:25 PMAPASS
permit finaled
FIR06-00858 INSP-Final Inspection7/14/20097/15/20097/15/2009 11:01:58 AMAPASS
Permit finaled as per stephanies inspection
FIR06-00857 INSP-Final Inspection7/14/20097/15/20097/15/2009 11:01:35 AMAPASS
Permit finaled as per stephanies inspection
FIR09-00238 INSP-Final Inspection7/14/20097/15/20097/15/2009 11:01:19 AMAPASS
Permit finaled. Fire alarm interconnection complete and tested by Forrest France
FIR07-00252 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:37:40 PMAPASS
Permit finaled as per inspection by Stephanie Cobbley
FIR07-00251 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:36:55 PMAPASS
Permit finaled as per inspection by Stephanie Cobbley.
FIR07-00250 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:36:12 PMAPASS
Permit finaled as per inspection by Stephanie Cobbley
FIR06-00862 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:35:23 PMAPASS
Permit finaled as per inspection by Stephanie Cobbley
FIR06-00861 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:34:42 PMAPASS
Permit finaled as per inspection by Stephanie Cobbley.
FIR06-00860 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:33:58 PMAPASS
Permit finaled as per inspection by Stephanie Cobbley
FIR06-00859 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:33:08 PMAPASS
Permit finaled as per Stephanie Cobbley.
FIR05-00753 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:31:32 PMAPASS
Permit finaled per requirement of last inspection entry. Items have been corrected.
FIR05-00752 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:30:30 PMAPASS
Permit finaled per requirement of last inspection entry. Notification coverage verified.
FIR05-00751 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:29:32 PMAPASS
Permit finaled per requirement of last inspection entry.
FIR05-00750 INSP-Final Inspection7/14/20097/15/20097/14/2009 2:28:53 PMAPASS
Permit finaled per requirement of last inspection entry.