FIR09-00033
| INSP-Sprinkler Rough-in | 7/8/2009 | 7/15/2009 | 7/16/2009 8:09:56 AM | P | PART |
|
|
Fire pump curve certification passed pending acceptance of the non-functioning PLD due to possible water surge. Lucas with Peerless Pump stated that this is not a problem during a fire condition. The pump provided 472 gpm at 150% which is more than required.
|
FIR09-00033
| INSP-Sprinkler Rough-in | 7/8/2009 | 7/15/2009 | 7/16/2009 8:07:32 AM | A | FAIL |
|
|
Time tests for double interlock preaction systems at freezers unable to be completed due valves could not be set up.
|
FIR09-00345
| INSP-Final Inspection | 7/15/2009 | 7/15/2009 | 7/15/2009 4:30:41 PM | P | CANC |
|
|
Cancelled due to time constraints. Rescheduled for tomorrow with life safety inspection.
|
FIR09-00395
| INSP-Sprinkler Rough-in | 7/15/2009 | 7/15/2009 | 7/15/2009 4:28:16 PM | P | CANC |
|
|
Cancelled due to time constraints. Rescheduled for tomorrow.
|
FIR09-00397
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 4:25:24 PM | A | PASS |
|
|
permit finaled
|
FIR09-00087
| INSP-Alarm Testing | 7/14/2009 | 7/15/2009 | 7/15/2009 2:02:39 PM | P | PASS |
|
|
Permit finaled.
|
BLD04-01154
| FIRE-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 2:02:05 PM | A | FAIL |
|
|
Provide emergency lights in the basement storage rooms and in the stairwell next to the elevator as per the approved plans. Provide exit signs in the basement storage rooms as per the life safety drawings or provide verification from the plan reviewer they can be deleted. The open DeBest Fire Protection FIR permits are to be disregarded.
|
FIR09-00255
| INSP-Sprinkler Rough-in/Hydro | 7/15/2009 | 7/15/2009 | 7/15/2009 12:53:31 PM | A | CANC |
|
|
duplicate inspection
|
BLD09-00453
| FIRE-Final Inspection | 7/15/2009 | 7/15/2009 | 7/15/2009 12:52:11 PM | P | PASS |
|
|
life safety passed
|
FIR09-00258
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:50:42 PM | P | PASS |
|
|
permit finaled
|
FIR09-00256
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:49:44 PM | P | PASS |
|
|
permit finaled
|
FIR09-00300
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:48:39 PM | A | PASS |
|
|
permit finaled
|
FIR09-00298
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:47:00 PM | A | PASS |
|
|
permit finaled
|
FIR09-00057
| FIR-Aging Inspection | 7/15/2009 | 7/15/2009 | 7/15/2009 12:24:56 PM | | NR |
|
|
wip
|
FIR08-00724
| INSP-Final Inspection | 7/15/2009 | 7/15/2009 | 7/15/2009 12:20:18 PM | P | CANC |
|
|
Please call 30 min prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton Inspection cancelled from web by: Jeff Walton
|
BLD09-00457
| FIRE-Final Inspection | 7/15/2009 | 7/15/2009 | 7/15/2009 12:14:06 PM | P | PASS |
|
|
life safety passed
|
BLD09-00455
| FIRE-Final Inspection | 7/15/2009 | 7/15/2009 | 7/15/2009 12:13:38 PM | P | PASS |
|
|
life safety passed
|
FIR09-00250
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:12:29 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00249
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:11:59 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00248
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:11:31 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00303
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:09:39 PM | A | PASS |
|
|
Permit finaled
|
FIR09-00302
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:09:04 PM | A | PASS |
|
|
Permit finaled
|
FIR09-00301
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 12:08:25 PM | A | PASS |
|
|
permit finaled
|
FIR06-00858
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 11:01:58 AM | A | PASS |
|
|
Permit finaled as per stephanies inspection
|
FIR06-00857
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 11:01:35 AM | A | PASS |
|
|
Permit finaled as per stephanies inspection
|
FIR09-00238
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/15/2009 11:01:19 AM | A | PASS |
|
|
Permit finaled. Fire alarm interconnection complete and tested by Forrest France
|
FIR07-00252
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:37:40 PM | A | PASS |
|
|
Permit finaled as per inspection by Stephanie Cobbley
|
FIR07-00251
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:36:55 PM | A | PASS |
|
|
Permit finaled as per inspection by Stephanie Cobbley.
|
FIR07-00250
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:36:12 PM | A | PASS |
|
|
Permit finaled as per inspection by Stephanie Cobbley
|
FIR06-00862
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:35:23 PM | A | PASS |
|
|
Permit finaled as per inspection by Stephanie Cobbley
|
FIR06-00861
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:34:42 PM | A | PASS |
|
|
Permit finaled as per inspection by Stephanie Cobbley.
|
FIR06-00860
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:33:58 PM | A | PASS |
|
|
Permit finaled as per inspection by Stephanie Cobbley
|
FIR06-00859
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:33:08 PM | A | PASS |
|
|
Permit finaled as per Stephanie Cobbley.
|
FIR05-00753
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:31:32 PM | A | PASS |
|
|
Permit finaled per requirement of last inspection entry. Items have been corrected.
|
FIR05-00752
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:30:30 PM | A | PASS |
|
|
Permit finaled per requirement of last inspection entry. Notification coverage verified.
|
FIR05-00751
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:29:32 PM | A | PASS |
|
|
Permit finaled per requirement of last inspection entry.
|
FIR05-00750
| INSP-Final Inspection | 7/14/2009 | 7/15/2009 | 7/14/2009 2:28:53 PM | A | PASS |
|
|
Permit finaled per requirement of last inspection entry.
|