FIR10-00540
| INSP-Sprinkler Rough-in | 7/14/2011 | 7/15/2011 | 7/15/2011 3:51:11 PM | P | PART |
|
|
Perimeter rooms at the third floor as marked on plans okayed for ceiling cover.
|
BLD11-00551
| FIRE-Final Inspection | 7/15/2011 | 7/15/2011 | 7/15/2011 3:47:18 PM | P | PASS |
|
|
Reinspection passed. Life safety finaled.
|
BLD11-01616
| FIRE-Final Inspection | 7/15/2011 | 7/15/2011 | 7/15/2011 3:24:37 PM | P | PASS |
|
|
Life safety inspection passed.
|
BLD09-01405
| BLD-Aging Inspection | 7/15/2011 | 7/15/2011 | 7/15/2011 3:23:40 PM | P | PEND |
|
|
Pending fire sprinkler work.
|
FIR08-00239
| INSP-Sprinkler Rough-in | 7/15/2011 | 7/15/2011 | 7/15/2011 3:22:52 PM | P | PART |
|
|
Okayed for cover amenity rooms, restrooms and concealed space adjacent to the electrical room- noted and marked with today's date.
|
FIR10-00583
| INSP-Sprinkler Rough-in/Hydro | 7/14/2011 | 7/15/2011 | 7/15/2011 3:20:44 PM | P | FAIL |
|
|
Overhead rough-in at the first floor completed. Noted corrections include; blocked upright at the kitchen, DP not yet installed at the cooler and freezer, missing EQ brace at the 2" main in the gym, replace ssu at classroom 102, overspaced upright and pendent at office 124, one upright at corridor 111 is obstructed, head at class 108 restroom needs relocated- see asterik plan annotations. Approved for cover remainder of classrooms and the faculty lounge as marked and dated.
|
FIR11-00208
| INSP-Final Inspection | 7/13/2011 | 7/15/2011 | 7/15/2011 2:27:49 PM | A | PART |
|
|
Fire alarm testing completed satisfactory- Final pending provision for item #28 on the fire code review comments regarding a knox box per BMC requirements.
|
BLD10-02863
| FIRE-Final Inspection | 7/14/2011 | 7/15/2011 | 7/15/2011 10:20:46 AM | A | PASS |
|
|
Fire life safety completed acceptable. Manual thumbturn at the main entry removed.
|
FIR11-00240
| INSP-Final Inspection | 7/14/2011 | 7/15/2011 | 7/15/2011 10:19:35 AM | A | PASS |
|
|
Fire sprinkler work passed inspection. *NOTE: Permit should be attatched to project related BLD10-02863 suite 430 on the 4th floor.
|
BLD11-00551
| FIRE-Final Inspection | 7/14/2011 | 7/15/2011 | 7/15/2011 10:02:54 AM | A | FAIL |
|
|
Duct detector failed to initiate unit shutdown upon smoke detection. Door hardware and signage corrections are finished.
|
BLD11-00760
| FIRE-Final Inspection | 7/14/2011 | 7/15/2011 | 7/15/2011 10:01:10 AM | A | PASS |
|
|
Noted correction items verified for completion. Fire life safety passed.
|
FIR11-00227
| INSP-Final Inspection | 7/14/2011 | 7/15/2011 | 7/15/2011 10:00:16 AM | A | PASS |
|
|
Fire sprinkler work passed final inspection. Permit finaled.
|