FIR13-00037
| INSP-Sprinkler Rough-in | 7/12/2013 | 7/15/2013 | 7/15/2013 3:56:20 PM | P | PASS |
|
|
Rough to cover passed for areas marked ok on the second floor.
|
BLD12-00452
| FIRE-Final Inspection | 7/15/2013 | 7/15/2013 | 7/15/2013 3:20:15 PM | P | FAIL |
|
|
Provide racking permit for racks exceeding 8' in height as per note #11 of the fire review and repair the exit sign/emergency light at the south exit
|
BLD12-02063
| BLD-Final | 7/15/2013 | 7/15/2013 | 7/15/2013 2:30:04 PM | P | PASS |
|
|
Fire life safety passed
|
BLD12-03273
| FIRE-Final Inspection | 7/12/2013 | 7/15/2013 | 7/15/2013 2:28:47 PM | P | CANC |
|
|
Cancel per Joe Phone #: ###-#### To be rescheduled for tomorrow morning.
|
FIR13-00175
| INSP-Sprinkler Rough-in/Hydro | 7/12/2013 | 7/15/2013 | 7/15/2013 2:25:41 PM | P | CANC |
|
|
Rescheduled for tomorrow morning.
|
FIR13-00148
| INSP-Final Inspection | 7/12/2013 | 7/15/2013 | 7/15/2013 2:02:00 PM | P | CANC |
|
|
We would like to schedule this with alarm testing and fire life safety final. Please call with time frame. Phone #: ###-#### >> Inspection requested via web by Jeff Packham Inspection cancelled from web by: Jeff Packham
|
FIR13-00116
| INSP-Sprinkler Rough-in | 7/15/2013 | 7/15/2013 | 7/15/2013 1:31:18 PM | P | PASS |
|
|
24 air test on dry system started at 1:30 with 45psi on the guage
|
FIR13-00214
| INSP-Sprinkler Rough-in | 7/15/2013 | 7/15/2013 | 7/15/2013 1:09:10 PM | P | PASS |
|
|
Todays inspection was a rough-in for the whole system. See locations circled in red where the sprinkler protection at the unit heaters has not been installed. Per Tim the EFSR heads located under/in the smoke vents are ok more than 18" from the deck. Per the drawings no earth quake bracing/retaining straps are required and none are installed. I did not look at the riser. The overhead hydro test of the dry system passed. A plan modifiction is required for the piping changes in the north office area and the heads under the overhead doors.
|
BLD13-00925
| FIRE-Final Inspection | 7/15/2013 | 7/15/2013 | 7/15/2013 10:36:18 AM | P | FAIL |
|
|
Provide fire extinguishers as discussed for both tenant spaces including the second floor areas. Provide doors that swing out, have approved hardware and have an exit sign per the approved plans from the Breakroom or get new approvals from plan review.
|
FIR13-00294
| INSP-Final Inspection | 7/12/2013 | 7/15/2013 | 7/15/2013 10:27:42 AM | A | CANC |
|
|
Cancel per Alex Phone #: ###-####
|
FIR13-00255
| INSP-Final Inspection | 7/12/2013 | 7/15/2013 | 7/15/2013 8:09:04 AM | A | FAIL |
|
|
Todays inspection was just a final for the "dry storage" area. Sprinklers are complete in this area but other areas are still under construction.
|